5.1 Optimum Environment
When installing the server in a rack, select a location that meets the environmental
standards described in this section.
5.1.1 Temperature Requirements
To ensure continued safe and reliable equipment operation, install or position the system in
a well-ventilated, climate-controlled environment.
The maximum recommended ambient operating temperature (TMRA) for most server products
is 35°C (95°F). The temperature in the room where the rack is located must not exceed 35°C (95°F).
CAUTION:
To reduce the risk of damage to the equipment when installing third-party options:
• Do not permit optional equipment to impede airflow around the server or to increase the
internal rack temperature beyond the maximum allowable limits.
• Do not exceed the manufacturer’s TMRA.
5.1.2 Power Requirements
Installation of this equipment must comply with local and regional electrical regulations
governing the installation of information technology equipment by licensed electricians.
This equipment is designed to operate in installations covered by NFPA 70, 1999 Edition
(National Electric Code) and NFPA-75, 1992 (code for Protection of Electronic Computer/
Data Processing Equipment). For electrical power ratings on options, refer to the product
rating label or the user documentation supplied with that option.
WARNING:
To reduce the risk of personal injury, fire, or damage to the equipment, do not
overload the AC supply branch circuit that provides power to the rack. Consult the electrical
authority having jurisdiction over wiring and installation requirements of your facility.
CAUTION:
Protect the server from power fluctuations and temporary interruptions with
a regulating uninterruptible power supply (UPS). This device protects the hardware from
damage caused by power surges and voltage spikes and keeps the system in operation
during a power failure.
Summary of Contents for NF5486M5
Page 1: ...Inspur Server User Manual NF5486M5 ...
Page 24: ...18 4 Remove the fan bracket from the chassis as shown by and remove the fan as shown by ...
Page 36: ...30 4 Remove the air baffle vertically and replace it with a new one ...
Page 112: ...106 ...
Page 113: ...107 BMC Settings ...
Page 114: ...108 ...
Page 115: ...109 BMC Settings ...
Page 120: ...114 ...
Page 121: ...115 BMC Settings ...
Page 122: ...116 ...