7.1.2
No Display
Symptoms:
After the power button has been pressed, the power LED on the power button
changes from orange to green, the system fans work normally, but there's no
output on the monitor.
Solutions:
1.
Check whether the monitor is powered up normally.
2.
If yes, but there is still no output on the monitor, check whether the monitor is
connected properly to the server's VGA port.
3.
If yes, but there is still no output on the monitor, replace with another monitor.
4.
If the problem still persists, maybe the VGA port is faulty. Log into the BMC Web
interface. Launch the BMC remote KVM (for details, refer to Section 4.5
Firmware Update and Configuration
) to see if there is normal output: If yes,
maybe the VGA port on the motherboard is abnormal, please contact Inspur
Customer Service; if no, please record the detailed warning information.
5.
If the instructions above do not resolve the problem, call Inspur Customer
Service Hotline (1-844-860-0011/1-760-769-1847) or email to
, and inform us of the detailed warning information
and failure.
7.1.3
Abnormal LED on the Front Panel
Symptoms:
The status LED on front panel illuminates red.
Solutions:
Identify the abnormal LED based on "Front Panel Buttons and LEDs".
1.
If the system status LED illuminates red, check whether the server is under
normal operation: If yes, log into the BMC Web interface to view the BMC logs
(For detailed reference document, see Section 4.5
Firmware Update and
Configuration
) to check whether there are warnings. If yes, record the detailed
warning information.
a.
If the power status LED is abnormal, check if the PSU LEDs on the rear
panel are abnormal (amber or off): If the PSU LEDs are normal, log into
the BMC Web interface to check the BMC logs (For detailed reference
document, see Section 4.5
Firmware Update and Configuration
) to check
whether there is an alarm. If yes, record the detailed warning information.
If all the PSU LEDs are abnormal, see “PSU LED Off or Illuminates Amber” in
the Section “Power-On Failure”.