61
INOVANCE TECHNOLOGY EUROPE GmbH
MD800 EtherCAT Starting Guide_EN_v1.1_20211109.docx
F4-11
DI6 terminal
function selection
0-63. See table below
Select the function of the input
terminal.
F4-12
DI7 hardware
source selection
See function code F4-00
setting range
Select the source of the input
terminal.
F4-13
DI7 terminal
function selection
0-63. See table below
Select the function of the input
terminal.
F4-14
DI8 hardware
source selection
See function code F4-00
setting range
Select the source of the input
terminal.
F4-15
DI8 terminal
function selection
0-63. See table below
Select the function of the input
terminal.
F4-17
Terminal command
mode
0: Two-wire type 1
Two-wire mode 1, access to 2
DI terminals, one is used to
control the start and stop of
the inverter in forward
rotation, and the other is
used to control the start and
stop of the reverse rotation.
1: Two-wire type 2
Two-wire mode 2, access 2 DI
terminals, one is used to
control the start and stop of
the inverter, and the other is
used to control the running
direction.
2: Three-wire 1
Three-wire mode 1, access 3
DI terminals, one is used to
control the start and stop of
the inverter, and the other 2
are used to control the
running direction.
3: Three-wire 2
Three-wire mode 2, access 3
DI terminals, one is used to
control the start of the
inverter, one is used to
control the stop, and the
other one is used to control
the running side to.
There are four different ways to
control the operation of the inverter
through external terminals.
F4-18
Terminal
UP/DOWN change
rate
0.001Hz/s~65.535Hz/s
The rate of change when adjusting the
frequency through the terminal UP or
DOWN When DI terminal function
selection is set to terminal UP or
terminal DOWN, this parameter needs
to be set (the value of F4-01~F4-15 is
6 or 7).
F4-19
DI1 delay time
0.0s~3600.0s
When the state of the digital input
terminal DI changes, the inverter
delay time for the change. Currently
only DI1, DI2, DI3 have set delay
F4-20
DI2 delay time
0.0s~3600.0s
When the state of the digital input
terminal DI changes, the inverter