- 40 -
Quick setup
* MC reaction time
: the reaction time of output relay of MC.
For some applications, the status of output contactor needs to be checked before AC
drive starts up, hence one relay output of MC will feedback to IGBT Enable (above in the
diagram it is DI6).
This function can work by assigning “IGBT Enable” function to a digital input, please
refer to the table below to set.
Take DI6 for example: assign “IGBT Enable” to DI6, then set F4-05=8. If it's necessary
to change active mode of IGBT Enable, then use F4-38 or F4-39 to set (low level or high
level active).
Parameter
Parameter Name
Setting Range
Unit
Default Commission
F4-00
DI1 function selection
0: No function
1: Forward RUN (FWD)
2: Reverse RUN (REV)
......
8: IGBT Enable
......
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
15: Multi-reference terminal 4
......
N.A
1
-
F4-01
DI2 function selection
N.A
2
-
F4-02
DI3 function selection
N.A
12
-
F4-03
DI4 function selection
N.A
13
-
F4-04
DI5 function selection
N.A
14
-
F4-05
DI6 function selection
N.A
0
8
F4-06
DI7 function selection
N.A
15
-
F4-07
DI8 function selection
N.A
0
-
F4-08
PTC function enable
(On-board expansion
card)
N.A
0
-
F4-38
DI active mode
selection
(Normal: low level
active)
DI5 active mode:
0: Normal
1: Opposite
DI4 active mode:
0: Normal
1: Opposite
DI3 active mode:
0: Normal
1: Opposite
DI2 active mode:
0: Normal
1: Opposite
DI1 active mode:
0: Normal
1: Opposite
7-segment
00000 to 11111 (binary)
N.A
00000
-