-101-
Introduction
%"
DPOWFSUFS
7
7
7
%$ %$
DPOWFSUFS
'JMUFS
7%$ FYUFSOBMQPXFS
7
$0.
*
7*
.PUPSESJWFNPEVMF
BOEPUIFST
Ē
UP
Ē
'(
"(/%
"(/%
7
Figure 5-45
Connection for current-controlled signal
NOTE
◆
*1 Use 2-core shielded twisted pair cable as power cable.
◆
*2 If noises or ripples are generated in external wiring
,
connect a capacitor of 0.1 to 0.47 mF 25 V
between terminals V+/I+ and VI-.
3) Wiring instructions
■
Do not bind the cable together with AC cable
,
main lines
,
high voltage cable and so forth; otherwise
,
increased noise
,
surge
,
and induction may be caused.
■
Apply single-point grounding for the shielding of shielded cable and solder sealed cable.
■
Tubed and solderless crimp terminal cannot be used with terminal block. Using marking sleeve or
insulation sleeve to cover the cable connector part of the crimp terminals is recommended.
5.6.5 Temperature Module
1
Terminal arrangement and signal definitions of the temperature module (AM600-4PT)
1)
Terminal arrangement and signal definitions
Terminal Arrangement
Terminal
Symbol
Type
Function
Terminal No.
RUN
ERR
IN0 A
Input
Temperature measuring resistor A of channel 0
1
IN0 B
Input
Temperature measuring resistor B of channel 0
3
IN0 b
Input
Temperature measuring resistor b of channel 0
5
IN1 A
Input
Temperature measuring resistor A of channel 1
2
IN1 B
Input
Temperature measuring resistor B of channel 1
4
IN1 b
Input
Temperature measuring resistor b of channel 1
6
IN2 A
Input
Temperature measuring resistor A of channel 2
9
IN2 B
Input
Temperature measuring resistor B of channel 2
11
IN2 b
Input
Temperature measuring resistor b of channel 2
13
IN3 A
Input
Temperature measuring resistor A of channel 3
10
IN3 B
Input
Temperature measuring resistor B of channel 3
12
IN3 b
Input
Temperature measuring resistor b of channel 3
14
NC
Reserved Reserved
7
NC
8
NC
15
NC
16
24 V
Power
+24 V power supply
17
COM
Power
24 V power ground
18