4.1 Installation Environment Requirements
4.1.1 Installation Environment
■
Consider operability
,
serviceability
,
environment endurance when installing the PLC on the guide
rail. Do not install the module in the following environment:
■
The ambient temperature is out of the range of -5 ℃ to 55 ℃
.
■
The ambient humidity is out of the range of 5% to 95%.
■
The temperature fluctuates dramatically
,
and moisture condensation occurs.
■
Corrosive or combustible gases exist.
■
A large amount of conductive powder such as dust and iron powder
,
oil mist
,
salt
,
or organic solvent
exists.
■
The module is exposed to direct sunlight.
■
Strong electric field or magnetic field exists.
■
The machine vibrates or is affected by passed-down impact.
4.1.2 Installation Clearance
To ensure good ventilation and simplify module replacement
,
reserve the clearance specified in the
following figure between the module and walls and components.
DC24V
39
40
2
1
C
N
5
CANERR
CANRUN
BF
SF
ERR
RUN
0 1 2 3
7
6
5
4
2
7
6
5
4
1
0
3
4 5 6 7
3
2
1
0
I
II
RUN/ STOP
MFK
≥
50
mm
m
≥
55 mm
≥
55 mm
Risk of electric shock
AM600
小心触电
C
N
3
E
th
erN
ET
C
N
4
E
the
rC
A
T
C
N
1
R
S
48
5
C
N
2
C
AN
≥
60 mm
≥
50
mm
Figure 4-1
nstallation clearance requirements
4.1.3 Installation Instructions
Comply with the following instructions during installation:
■
Power off the product before installation.
■
Avoid drop-off and impact of the housing
,
terminal block
,
and connector of the module to prevent
damages.
■
Do not disassemble the module.
■
Do not tighten the machine with excessive torque to avoid damaging terminals.
■
After installation and commissioning
,
remove the anti-dust label from the heat dissipation holes on
the top of the module to ensure module reliability when the temperature rises.