The following settings are for automatically sending 
emails to specified email addresses.

Under 

Current email events

 you can have an email 

sent automatically in the following events:

Code Event

Description

1

Status change

An email is sent every time the 
status changes

2

After each FT

An email is sent after every 
function test

3

Start/end of DT The module sends an email at 

the start and end of a battery 
duration test

4

Fault

The module sends an email to 
the recipients if one of the fol-
lowing faults is identified:
- battery voltage too high
- battery voltage too low
- battery open circuit

5

Power failure

An email is sent when a power 
failure affects the main or sub-
distribution board

6

Blocked

The specified users receive an 
email if the device is blocked

You can enter multiple codes in this field. Spaces are 
ignored. If you enter "2 3 5" or "235", an email is sent 
after a function test, during the battery duration test, 
and in the event of a power failure.

Leaving the 

Email event

 field blank means no emails 

are automatically sent.

Enter the email server you want to use under 

Current 

SMTP server

. This can be an IP address or a DNS name 

but the entry may not exceed 40 characters.

Current sender email address

 specifies the email 

sender. This may not exceed 40 characters.

Under 

Current recipient email address

 enter the email 

recipient. Again, you can enter up to 40 characters. If you 
want several users to receive an email, this recipient will 
have to forward the mail to them.

If you want to request authentication to send an email 
by way of "POP before SMTP", you can activate this under 

Current POP3 server

Current login user name

 and 

New login password

. The password is not shown in plain 

text.

If you entered a DNS name instead of an IP address for 
the servers, you need to enter the IP address of a DNS 
server under 

IP address DNS server

 to cancel the name. 

This is not necessary if an address was automatically 
obtained by DHCP.

Die nachfolgenden Einstellungen sind zum automa-
tischen Versenden von Emails an die angegebenen 
Email-Adressen.

Im Feld 

Aktuelle Email Ereignisse

 können bei folgenden 

Ereignissen eine automatische Email verschickt werden:

Kenn-
ziffer

Ereignis

Beschreibung

1

Status ändert 
sich

Bei jeder Statusänderung wird 
eine Email versendet.

2

Nach jedem FT Nach jedem Funktionstest wird 

eine Email versendet.

3

Bei BT Start/
Ende

Bei Start und bei Ende eines 
Betriebsdauertest versendet 
das Modul eine Email

4

Bei Störung

Wenn eine der folgenden Stö-
rungen erkannt wird, sendet 
das Modul eine Email an die 
Empfänger:
- Batteriespannung zu hoch
- Batteriespannung zu tief
- Batterieunterbrechung

5

Bei Netzausfall

Sowohl bei Netzausfall der 
Hauptverteilung als auch der 
Unterverteilung wird eine 
Email versendet

6

Blocked

Wenn das Gerät blockiert wird 
erhalten die angegebenen 
Benutzer eine Email

Es können in dem Feld mehrere Kennziffern eingegeben wer-
den. Leerzeichen werden dabei nicht berücksichtigt. Bei einer 
Eingabe von „2 3 5“ bzw. „235“ wird eine Email nach einem Funk-
tionstest, bei Betriebsdauertest und bei Netzausfall versendet.

Wenn als 

Email Ereignis

 nur ein Leerzeichen eingegeben 

wird, so ist das automatische Senden von Emails nicht aktiv.

Der zu benutzende Email-Server wird im Feld 

Aktuelle 

SMTP Server

 eingetragen. Hier kann sowohl die IP-

Adresse als auch ein DNS-Name angegeben werden. 
Die Eingabe ist auf 40 Zeichen beschränkt.

Aktuelle Sender E-Mail Adresse

 gibt den Absender der Email 

an. Die Angabe darf nicht länger als 40 Zeichen sein.

Im Feld 

Aktuelle Empfänger E-Mail Adresse

 wird der 

Email-Empfänger eingetragen. Auch hier sind nur 40 Zei-
chen zulässig. Wenn mehrere Benutzer eine Email erhal-
ten sollen, so muss dies mit einer Weiterleitung der Email 
von diesem Empfänger erfolgen.

Falls zum Senden der Email vorher eine Authentifizierung 
per „POP before SMTP“ notwendig ist, so kann in den Fel-
dern 

Aktuelle POP3-Server

Aktueller Login Benutzer-

name

 und 

Neues Login Passwort

 dieses aktiviert werden. 

Das Passwort wird nicht im Klartext angezeigt.
Wenn bei den Servern ein DNS-Name angegeben wurde 
anstatt der IP-Adresse so muss im Feld 

IP-Adresse DNS 

Server

 die IP-Adresse eines DNS-Servers zur Namensauflö-

sung angegeben werden. Die Angabe ist nicht nötig, wenn 
per DHCP eine Adresse automatisch bezogen wurde.

Summary of Contents for CLS 24.1

Page 1: ...heitstechnik GmbH Mounting and Operating Instructions Emergency Lighting Device CLS 24 1 7Ah CLS 24 1 CLS 24 1 Power Montage und Betriebsanleitung Notlichtversorgungsger t CLS 24 1 7Ah CLS 24 1 CLS 24...

Page 2: ......

Page 3: ...3 Montage und Betriebsanleitung Notlichtversorgungsger t CLS 24 1 7Ah CLS 24 1 CLS 24 1 Power Mounting and Operating Instructions Emergency Lighting Device CLS 24 1 7Ah CLS 24 1 CLS 24 1 Power...

Page 4: ...achung 50 12 4 Protokolle zu wiederkehrenden Pr fungen 51 Anhang 52 A Kopiervorlage f r die Anlagendokumentation 52 B Stromaufnahmetabellen 56 C Leitungsl ngen 56 D Kundendienst 57 Contents 1 General...

Page 5: ...connected lumi naires is corrected a function test must be carried out to reset the fault indication 8 3 1 Running a function test page 24 1 Allgemeine Hinweise 1 1 Symbolerkl rung Sicherheitsrelevan...

Page 6: ...interrupted for an extended period of time the battery circuit must be disconnected by removing the battery fuse in accordance with the operating instructions 7 Commissioning the CLS device page 21 C...

Page 7: ...odule INOLan the CLS sys tem is monitored with the INOTEC software INOView 4 Produktbeschreibung Die dezentrale INOTEC Notlichtanlage CLS 24 1 ist ein Versorgungsger t in Schutzklasse I f r den Betrie...

Page 8: ...in On St rung Failure SK 3 Ein On St rung Failure SK 4 Ein On St rung Failure Netz N L LSA1 N L LSA2 N L LSA3 N L LSA4 L PE N R T G IBa IBp IBp 24V T FS SL 24V Opt Stoer Betr Bat B SK1 SK2 SK3 SK4 1 2...

Page 9: ...Operation Batt Betrieb Batt Operation St rung Failure Lade St rung Charge Failure SK 1 Ein On St rung Failure SK 2 Ein On St rung Failure SK 3 Ein On St rung Failure SK 4 Ein On St rung Failure Netz...

Page 10: ...fuse 5AT AV 50A Noise level 0 dB Dimensions 345 x 245 x 112 Weight 9 6 kg Battery 24V 7 2Ah Battery power 1h 2 7A 3h 1 7A Dimensioned drawing 5 Technische Daten 5 1 CLS 24 1 7Ah Anschlussspannung 230V...

Page 11: ...7 kg Batterie 24V 12Ah 24V 24Ah Batteriestrom 1h 6 6A 3h 2 9A 8h 1 3A 1h 6 6A 3h 5 8A 8h 2 6A Ma bild 5 2 CLS 24 1 Connection voltage 230V AC 10 Terminal mains supply 4 mm Mains fuse 5AT AV 1500A Outp...

Page 12: ...e CLS 24 1 und CLS 24 1 7Ah is supplied with batteries installed The emergency lighting device CLS 24 1 Power is sup plied without installed batteries 5 3 CLS 24 1 Power Anschlussspannung 230V AC 10 K...

Page 13: ...s have to be mounted on the top of the lower batteries if 4 batteries are installed in the steel cabinet 6 1 Ger t CLS 24 1 Nach dem Auspacken entfernen Sie im lie genden Zustand die vordere Schraube...

Page 14: ...Bp IBp 24V T FS SL 24V Opt Stoer Betr Bat B SK1 SK2 SK3 SK4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Betrieb Operation Batt Betrieb Batt Operation St rung Failure Lade St rung Charge Failure...

Page 15: ...htung und Sicher heitsleuchten gemeinsam geschaltet werden so kann unten stehende Schaltung angewendet werden Die Ein g nge sind f r 230V ausgelegt Dabei k nnen jeder ein zelnen Leuchte bis zu zwei Sc...

Page 16: ...berwachung anzuschlie en Bei Ausfall wird die 24V Stromschleife unterbrochen und alle Leuchten der Sicherheitsbeleuch tung schalten in den Notlichtbetrieb Bei berwachung von mehreren Unterverteilern...

Page 17: ...eral lighting General lighting General lighting Anschluss bei berwachung mit dreiphasigem Netz Supply monitoring in three phase installation Letzte DP Zener abschluss Last DP Zener diode termination s...

Page 18: ...max 500m min 0 5mm Bei der Angabe der Leitungsl nge handelt es sich um die max Gesamtl nge Diese beinhaltet alle Leitungsstr nge incl Stiche Ein gleichzeitiger Betrieb von RTG Bus und INO Web oder IN...

Page 19: ...kte des Fernschalters sind werksseitig gebr ckt ber diesen ist es m glich die Dauerlichtleuchten des Systems zu blockieren Potentialfreie Meldekontakte max 24V 1A DC An den 24V Ausgangsklemmen kann ei...

Page 20: ...ieb schalten die Leuchten automatisch auf 100 HUB Switch InoWeb Control CLS InoWeb CLS InoWeb CLS InoWeb CLS InoWeb CLS InoWeb HUB Switch CLS InoWeb max 100m max 100m max 100m max 100m max 100m max 10...

Page 21: ...with monitoring loop function deactivated Remote switch with monitoring loop function deactivated Emergency lighting delay 0 minutes Manual reset deactivated All electric circuits are activated 7 Inbe...

Page 22: ...ilure Lade St rung Charge Failure Ein On St rung Failure Ein On St rung Failure Ein On St rung Failure Ein On St rung Failure F T C L S 2 4 V B e t r i e b U 2 7 5 V I 0 0 A 8 Use 1 2 3 4 5 6 7 8 9 10...

Page 23: ...4 1 Pr fbuch anzeigen 34 5 4 2 Pr fbuch ausgeben 35 5 4 3 Pr fbuch l schen 35 6 Blockierung aufheben 36 8 2 Menu structure Press OK to go to the main menu 3 Test menu 3 1 Running a function test 24 3...

Page 24: ...st to run on The CLS system will then start the function test at the specified time each week 8 3 Testmen 8 3 1 Funktionstest starten Im Funktionstestmodus schaltet das Ger t in den Bat teriebetrieb u...

Page 25: ...ntralen berwachung des CLS Ger tes ber das Meldetableau wird in diesem Men punkt die Ger te adresse vergeben 0 32 Die Einstellung 0 deaktiviert die Datenkommunikation f r das Meldetableau 8 3 6 Automa...

Page 26: ...hleife Seite 16 8 4 1 7 Notlicht Nachlauf 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 E i n s t e l l e n d e r N o t l i c h t N a c h l a u f Z e i t 1 0 m i n If the system is monitored usin...

Page 27: ...ion t program 8 programm device 8 destination 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 d e s t i n a t i o n E n t r y Bei R ckkehr der Netzversorgung bleiben alle Leuchten f r die angegeben...

Page 28: ...2 13 14 15 16 17 18 19 20 c i r c u i t 1 p r e s s O K t o d e o r a c t i v a t e X X X Faults in deregistered circuits are not displayed In dem Ger t kann ein Zielort mit maximal 20 Zeichen hinterl...

Page 29: ...r the Config luminaires menu You can choose between 3 operating modes for each luminaire 8 4 2 2 Stromkreis Zielorte Zu jedem Endstromkreis kann noch ein Zielorttext ein gegeben werden Dazu w hlen Sie...

Page 30: ...ered luminaire in the active circuit During destination description input all con nected luminaires switch to maintained light 8 4 3 1 Bereitschaftslicht BL Im Normalbetrieb ist die Leuchte ausgeschal...

Page 31: ...stests notwendig 8 4 7 Blockierung t Programmierung 8 Blockierung 8 Das Ger t blockiert die im Optionsmen 8 4 1 10 Blockieren von Seite 23 angegebenen Betriebsarten Dauerlichtbetrieb oder Dauer und N...

Page 32: ...ymbol The name must be no longer than 8 characters 8 4 8 INOSTICK 8 4 8 1 Konfiguration laden t Programmierung 8 INOSTICK 8 Konfig laden 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 W h l e n...

Page 33: ...n m a i n e n t r a n c e X X X X X X X Press 8 to display additional information about the luminaire such as the individual addresses and switching modes Falls der Dateiname schon vorhanden ist so m...

Page 34: ...ts are stored in the logbook 8 5 4 1 Displaying the logbook t info 8 logbook 8 display logbook 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 L e u c h t e 3 S K 2 I n d A d r 1 3 4 1 2 Taste ES...

Page 35: ...logbook 8 Use this command to delete the entire contents of the logbook 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 E i n t r a g N r 2 5 3 D a t u m 1 2 0 6 2 0 0 8 U h r z e i t 1 4 4 8 2 4 F...

Page 36: ...ei einer Leuchtenst rung berpr ft werden Individuelle Adresse korrekt Leuchtmittel OK Spannung am Eingang der Leuchte vorhanden 24V DC Elektronik defekt Leuchtenst rungen werden nach erfolgter Behebun...

Page 37: ...nterverteilungen berwacht wer den so m ssen die Klemmen SL SL gebr ckt sein Mittels einer Br cke zwischen SL SL kann die Funktionsf higkeit der Stromschleife berpr ft werden 9 2 Battery fault 1 2 3 4...

Page 38: ...d wird die Anlage mit Standort und Sta tusanzeigen wie Batteriestrom und Batteriespannung sowie den Zust nden der einzelnen Leuchten in den vier Stromkreisen dargestellt 10 INOWeb You can use the INOW...

Page 39: ...n Leuchten und dessen Zielorttext 10 2 St rungsausdruck Ein St rungsausdruck erfolgt ber die Druckfunktion des Webbrowsers Ein Ausdruck der Seite ist ber Datei Drucken m glich You can use the followin...

Page 40: ...terial Leuchte 07 OK Besprechungsraum Leuchte 08 OK Ausgang S dseite Leuchte 09 OK R107 Einkauf Leuchte 10 OK R103 Entwicklung Stromkreis 2 OK Lager Stromkreis 3 OK Stromkreis 4 OK 10 3 Automatic emai...

Page 41: ...the following values Bits per second 9600 Data bits 8 Parity None Stop bits 1 Flow control None 10 4 Programmierung Die Programmierung des Moduls erfolgt ber die serielle Schnittstelle im CLS System m...

Page 42: ...up 5 Normally the board will automatically negotiate with the network hub or switch to determine the Ethernet duplex setting however some hubs do not support autonegotiation In this case the Eth ernet...

Page 43: ...M connectme_lsk APPLICATION INOWeb APP SetupDialog 1 3 NETWORK INTERFACE PARAMETERS IP address on LAN is 192 168 100 200 LAN interface s subnet mask is 255 255 255 0 IP address of default gateway to o...

Page 44: ...und kann nicht ge ndert werden Eingabe Passwort HTML Seite TimeOut abwarten keine nderung Eingabe max 40 Zeichen Orts Bezeichnung TimeOut keine nderung Eingabe Ziffer nach welchem Ereignis E Mail ver...

Page 45: ...tgelegt werden Dieses wird zum Zugriff auf die Webseiten ben tigt Der Standarduser ist WEBUSER Durch Eingabe eines Leerzeichen erfolgt keine Passwortabfrage bei Aufruf der Informationsseite If nothing...

Page 46: ...Einstellungen sind zum automa tischen Versenden von Emails an die angegebenen Email Adressen Im Feld Aktuelle Email Ereignisse k nnen bei folgenden Ereignissen eine automatische Email verschickt werde...

Page 47: ...t entpackt wurde kann es ohne Installation gestartet werden Ein gr ner Haken neben dem Feld Apache deutet an dass der Webserver gestartet wurde Unter Settings k nnen Einstellungen zum Starten des Webs...

Page 48: ...rs welche im Internet zu finden ist 11 INOLan ber eine optional integrierte Netzwerkschnittstelle INOLan wird das CLS System mittels der INOTEC Soft ware INOView berwacht und Zustands nderungen in ein...

Page 49: ...unction check it must be possible to operate all safety lights in battery mode and each light must be checked to ensure that it functions 12 Pr fungen Das Notlichtger t ist nach den national g ltigen...

Page 50: ...pection and monitoring points as well as their time intervals can be found in the operating instructions of the battery manu facturer concerned und jede Leuchte ist auf korrekte Funktion zu berpr fen...

Page 51: ...bl cke sowie der gesamten Batterie bei Belastungsbeginn und ende Der schriftliche Nachweis ber die j hrliche War tung ist die Grundlage f r m gliche Garantieanspr che 12 4 Protocols for repeat tests T...

Page 52: ...om Power A A Zielort max 20 Zeichen einschl Leerzeichen Destination max 20 characters including spaces Gesamtstrom Total power Leuchten Typ Luminaries Type Dim 2 Dim 2 Kanal Nr 2 Channel no 2 Dim 1 Di...

Page 53: ...m Power A A Zielort max 20 Zeichen einschl Leerzeichen Destination max 20 characters including spaces Gesamtstrom Total power Leuchten Typ Luminaries Type Dim 2 Dim 2 Kanal Nr 2 Channel no 2 Dim 1 Dim...

Page 54: ...m Power A A Zielort max 20 Zeichen einschl Leerzeichen Destination max 20 characters including spaces Gesamtstrom Total power Leuchten Typ Luminaries Type Dim 2 Dim 2 Kanal Nr 2 Channel no 2 Dim 1 Dim...

Page 55: ...m Power A A Zielort max 20 Zeichen einschl Leerzeichen Destination max 20 characters including spaces Gesamtstrom Total power Leuchten Typ Luminaries Type Dim 2 Dim 2 Kanal Nr 2 Channel no 2 Dim 1 Dim...

Page 56: ...1018 SNP 1118 SN 8124 1 41 SN 9124 1 41 SN 804 SN 2518 4 x LED 1W 0 200A SNP 1016 SNP 1116 SN 6204 3 x LED 1W 0 150A SN 6114 SN 6109 SN 6205 SNP 7188 SNP 7286 2 x LED 1W 0 115A SNP 7186 SN 8124 1 11 S...

Page 57: ...49 0 29 38 97 30 0 Fax 49 0 29 38 97 30 29 www inotec licht de info inotec licht de Specifications are subject to change D Kundendienst Bevor Sie den Kundendienst beauftragen berpr fen Sie bitte folg...

Page 58: ...CLS 24 1 SV Montage und Betriebsanleitung CLS 24 1 SV Mounting and Operating Instructions 58...

Page 59: ......

Page 60: ...60 Sicherheitstechnik GmbH INOTEC Sicherheitstechnik GmbH Am Buschgarten 17 D 59 469 Ense Tel 49 29 38 97 30 0 Fax 49 29 38 97 30 29 info inotec licht de www inotec licht de 708 120 H 2017 05...

Reviews: