CLS 24.1/SV
Montage- und Betriebsanleitung
CLS 24.1/SV
Mounting and Operating Instructions
14
6.3. Electrical connection
The cabelling for the CLS 24.1 and CLS 24.1 - Power is via
the upper cable inlets.
A rear side cable inlet is possible for the surface-
mounted housing. Therefore the pre-stamped
steel metal at the rear has to be breaked out.
6.3.1. Mains connection
Connect the 230V AC voltage supply to terminals L,
N and PE.
6.3.2. Final circuits
The CLS system has 4 final circuits (2 final circuits at CLS
24.1-7Ah) to each monitor 20 luminaire addresses. The
final circuits can each carry a load of max. 3A with a 5A
fuse. Please make sure the total load on the entire system
is not exceeded.
5. Technical data - page 10
Using low voltage (SELV) to supply the emergency light-
ing simplifies cabling and eliminates the need for a PE
conductor. Please observe the wire lengths specified in
Appendix - Seite 56
The luminaires are connected at ter and -, of
which there are 2 per final circuit. Each luminaire has a
unique ID which you must then assign to a local address
on the circuit when you program it.
8.4.3. Program-
ming luminaires - page 29
When (un)installing the luminaires, make sure
the IDs on the casing and the module match.
In the event of replacement installation, make sure an
identical luminaire ID is not connected more than once
to a circuit of a CLS.
Max. wire length of final circuits
Appendix B. Input
power charts - Seite 56
6.3. Elektrischer Anschluss
Die Verkabelung erfolgt bei der CLS 24.1 und CLS 24.1 -
Power über die oberen Kabeleinführungen.
Im Aufputzgehäuse der CLS ist auch eine rücksei-
tige Kabeleinführung möglich. Dazu ist das vorge-
stanzte Blech in der Gehäuserückwand
herauszubrechen.
Netz
N L
LSA1
N L
LSA2
N L
LSA3
N L
LSA4
L
PE
N
R T G
IBa
IBp
IBp
+24V
T
FS
SL
+
–
+
–
+24V
+
–
Opt.
Stoer
Betr.
Bat.-B.
SK1
-
+
-
+
SK2
-
+
-
+
SK3
-
+
-
+
SK4
-
+
-
+
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Betrieb
Operation
Batt.-Betrieb
Batt.-Operation
Störung
Failure
Lade Störung
Charge Failure
SK 1
Ein
On
Störung
Failure
SK 2
Ein
On
Störung
Failure
SK 3
Ein
On
Störung
Failure
SK 4
Ein
On
Störung
Failure
N
etzanschluss
M
ains
conne
ction
Lich
tschalt
er
abfr
age
Lig
h
t sequen
ce swi
tching
Lich
tschalt
er
abfr
age
Lig
h
t sequen
ce swi
tching
Lich
tschalt
er
abfr
age
Lig
h
t sequen
ce swi
tching
Lich
tschalt
er
abfr
age
Lig
h
t sequen
ce swi
tching
CLS MTB
DPÜ
Th
ree-phase-moni
tor
M
eldetableau
M
imic panel
Leuch
te 1 ...
20
Lumina
ries 1…20
Leuch
te 1 ...
20
Lumina
ries 1…20
Leuch
te 1 ...
20
Lumina
ries 1…20
Leuch
te 1 ...
20
Lumina
ries 1…20
INOWeb
INOLan
Ex
ter
ne K
omp
onen
ten
Ex
te
rnal
com
p
one
n
ts
CLS D
immer
O
hne F
unktion
Not in use
6.3.1. Netzanschluss
Anschluss der Spannungsversorgung 230V AC an die
Klemmen L, N, PE.
6.3.2. Endstromkreise
Das CLS-System besitzt 4 Endstromkreise (2 Endstrom-
kreise bei CLS-7Ah) zur Überwachung von je 20 Leuch-
tenadressen. Die Endstromkreise können jeweils mit bis
zu max. 3A belastet werden und sind mit 5A abgesichert.
Dabei ist aber auf die Gesamtbelastung des ganzen Sys-
tems zu achten.
5. Technische Daten - Seite 10
Der Einsatz von Kleinspannung (SELV) zur Versorgung
der Notbeleuchtung vereinfacht die Verkabelung und
eine PE-Ader entfällt. Bitte beachten Sie dazu die Anga-
ben zur Leitungslänge im
Anhang - Seite 56
Über die K und -, die pro Endstromkreis
doppelt ausgeführt sind, werden die Leuchten ange-
schlossen. Jede Leuchte besitzt eine eindeutige ID, die
dann bei der Programmierung einer lokalen Adresse im
Stromkreis zugeordnet werden muss.
8.4.3. Leuchten
programmieren - Seite 29
Bei der De-/Montage der Leuchten ist darauf
zu achten, dass die IDs auf Gehäuse und Modul
übereinstimmen!
Im Fall der Nachinstallation ist darauf zu achten, dass
jede Leuchten-ID pro Stromkreis nur einmal an der CLS
angeschlossen wird!
Max. Leitungslänge Endstromkreis
Anhang - Seite
56
Summary of Contents for CLS 24.1
Page 2: ......
Page 58: ...CLS 24 1 SV Montage und Betriebsanleitung CLS 24 1 SV Mounting and Operating Instructions 58...
Page 59: ......