Icon
Mode
Status
Humidify
Humidify&Dehumidify
OFF
Humidify
Humidify&Dehumidify
ON
Humidify
Humidify&Dehumidify
OFF
Humidify
Humidify&Dehumidify
ON
Low Humi
protection value
Deadband
Deadband
High Humi
protection value
Humidification
on value
Adaption
range
Dehumidification
on value
[Humidify]
target value: When the current humidity of the device is lower than this value, then the
humidification will be started. The target value set needs to be lower than the high humidity protection
value minus the deadband value, and needs to be higher than the low humidity protection value.
[Dehumidify]
target value: When the current humidity of the device is higher than this value, then
the dehumidification will be started. The target value set needs to be higher than the low humidity
protection value plus the deadband value, and needs to be lower than the high humidity protection
value.
[Deadband]
value: The value set needs to be lower than (Dehumidification target value-Humidifica-
tion target value)/2 and the value needs to be greater than 0.
[Low Humi Protection]
value: The value set needs to be lower than the [Humidify] target value.
[High Humi Protection]
value: The value set needs to be higher than the [Dehumidify] target
value.
After the [Humidify] + [Deadband] value is reached, the humidification output port is turned off immedi-
ately.
In Dehumidify mode, the device will turn on the dehumidification output port when the current value is
higher than [Dehumidify] value, and immediately turn off the dehumidification output port when the
humidity value is lower than [Dehumidify]-[Deadband] value.
In Humidify & Dehumidify mode, the device will turn on the humidification output port when the current
value is lower than [Humidify] value, and immediately turn off the humidification output port when the
humidity value is higher than [Humidify] + [Deadband] value. The device will turn on the dehumidifica-
tion output port when the current value is higher than [Dehumidify] value, and immediately turn off the
dehumidification output port when the humidity value is lower than [Dehumidify]-[Deadband] value.
(6.2) Displaying current working status
When performing actions, the current device will display the specific working status of the device.
In different modes, different icons are used to display the current working status.
27