Wiring Analog Outputs (main unit only)
Maximum current output: 10 mA
Maximum connection cable length: less than 10 m
0-10V Output
(max 5 per device)
Actuator on 0-10V or PWM output example
Wiring the RS485 networks
Some useful links to our knowledge base website:
How to wire an RS485 network https://know.innon.com/howtowire-non-optoisolated
How to terminate and bias an RS485 network https://know.innon.com/bias-termination-rs485-network
Note:
the RS485 ports are not opto-isolated. Carefully check the orientation of the G and G0 terminals on all
devices to be the same and the shield to be connected correctly to avoid damaging the units.
RS485 between main unit and expansions
RS485 between main unit and BMS (*RS version)