Configure I/O
Universal Channels
Universal Channels are flexible connections that can be configured either as Inputs or Outputs with many
different types of signals available to be configured.
Check the following table to have an overview of all the possible configurations.
Please refer to the
column “Max per device” to know the configuration limit
s of each device
.
I/O
Group
Type
Max per
device
Filter/Speed
/Current
Input
Temperature
sensors
(passive inputs)
NTC 10K3A1
10
Filter: 0-9
0= fast reading,
no interpolation
9= slow reading, 9
readings
interpolation
NTC 10K4A1
10
NTC CAREL
10
PT1000
10
PT500
10
PT100 (3 wires, 2 inputs,
requires the next input to be
configured as “NOT USED”
)
5
PTC_R
10
NTC 0-150 CAREL
10
NTC -50T90 CAREL
10
NTC -10T170 CAREL
10
Active analog
inputs
0-1V
10
0-10V
10
0-5V (power from Link)
2
0-5V (external power supply)
10
0-20mA
4
4-20mA
Digital inputs
(clean contact)
DIGITAL INPUT
10
Speed:
FAST-NORMAL
Pulse/Frequency
counter input
PULSE COUNT
2
Current:
50uA
500uA
TTL level
For transistor out
reading
FREQUENCY MEASURE
Output
0-10V
0-10V
5
Not applicable
PWM
PWM 100Hz
10
PWM 2kHz
10