![Innon Link IO Manual Download Page 47](http://html.mh-extra.com/html/innon/link-io/link-io_manual_2062919047.webp)
Document name: Link IO - Manual
Document date: 1.2 10/02/2020
47
HoldingRegister
n41
32
Hysteresis Thermostat 1
Float
2.0
-999.9
999.9
ReadWrite
HoldingRegister
n43
32
Setpoint Thermostat 2
Float
25.0
-999.9
999.9
ReadWrite
HoldingRegister
n45
32
Hysteresis Thermostat 2
Float
2.0
-999.9
999.9
ReadWrite
ModbusData
Index
Bit
Variable Description
DataType
Default
Min
Max
Direction
InputRegister
n01
32
Current Value Universal Channel 1
Float
Read
InputRegister
n03
32
Current Value Universal Channel 2
Float
Read
InputRegister
n05
32
Current Value Universal Channel 3
Float
Read
InputRegister
n07
32
Current Value Universal Channel 4
Float
Read
InputRegister
n09
32
Current Value Universal Channel 5
Float
Read
InputRegister
n11
32
Current Value Universal Channel 6
Float
Read
InputRegister
n13
32
Current Value Universal Channel 7
Float
Read
InputRegister
n15
32
Current Value Universal Channel 8
Float
Read
InputRegister
n17
32
Current Value Universal Channel 9
Float
Read
InputRegister
n19
32
Current Value Universal Channel 10
Float
Read
InputRegister
n25
16
Auto/Manual Universal Ch Outputs
Bit-Field
Read
InputRegister
n26
16
Function status Universal Ch Outputs
Bit-Field
Read
InputRegister
n27
16
Auto/Manual Digital Outputs
Bit-Field
Read
InputRegister
n28
16
Function status Digital Outputs
Bit-Field
Read
InputRegister
n31
32
Current Value of Counter 1
Float
Read
InputRegister
n33
32
Current Value of Counter 2
Float
Read