Document name: Link IO - Manual
Document date: 1.2 10/02/2020
48
BACnet
Use this point list to configure your BMS BACnet supervisor (MSTP or IP depending on the used
device/connection)
Bit-field data type (Positive Integer Value BACnet Data) uses individual bits from the 16 bits available on the
point to provide multiple Boolean information.
Bit 0 refers to Universal channel 1, Digital output 1 or Analog output 1 (based on the point), Bit 1 refers to
Universal channel 2, Digital output 2 or Analog output 2 and so on.
Local
BACnet Data
ID
COV
Variable Description
DataType
Default
--
--
Direction
Binary Value
11
No
Command Digital Output 1
Bool
0
0
1
ReadWrite
Binary Value
12
No
Command Digital Output 2
Bool
0
0
1
ReadWrite
Binary Value
13
No
Command Digital Output 3
Bool
0
0
1
ReadWrite
Binary Value
14
No
Command Digital Output 4
Bool
0
0
1
ReadWrite
Binary Value
15
No
Command Digital Output 5
Bool
0
0
1
ReadWrite
Binary Value
16
No
Command Digital Output 6
Bool
0
0
1
ReadWrite
Binary Value
21
No
Reset Pulse Counter 1
Bool
0
0
1
ReadWrite
Binary Value
22
No
Reset Pulse Counter 2
Bool
0
0
1
ReadWrite
Binary Value
23
No
Preset Pulse Counter 1
Bool
0
0
1
ReadWrite
Binary Value
24
No
Preset Pulse Counter 2
Bool
0
0
1
ReadWrite
BACnet Data
ID
COV
Variable Description
DataType
Default
--
--
Direction
Binary Input
1
Yes
Digital Input Universal Channel 1
Bool
Read
Binary Input
2
Yes
Digital Input Universal Channel 2
Bool
Read
Binary Input
3
Yes
Digital Input Universal Channel 3
Bool
Read
Binary Input
4
Yes
Digital Input Universal Channel 4
Bool
Read
Binary Input
5
Yes
Digital Input Universal Channel 5
Bool
Read
Binary Input
6
Yes
Digital Input Universal Channel 6
Bool
Read
Binary Input
7
Yes
Digital Input Universal Channel 7
Bool
Read
Binary Input
8
Yes
Digital Input Universal Channel 8
Bool
Read
Binary Input
9
Yes
Digital Input Universal Channel 9
Bool
Read
Binary Input
10
Yes
Digital Input Universal Channel 10
Bool
Read
Binary Input
11
Yes
Current value Digital Output 1
Bool
Read
Binary Input
12
Yes
Current value Digital Output 2
Bool
Read
Binary Input
13
Yes
Current value Digital Output 3
Bool
Read
Binary Input
14
Yes
Current value Digital Output 4
Bool
Read
Binary Input
15
Yes
Current value Digital Output 5
Bool
Read
Binary Input
16
Yes
Current value Digital Output 6
Bool
Read
Binary Input
17
Yes
Digital Input ID 1
Bool
Read
Binary Input
18
Yes
Digital Input ID 2
Bool
Read
BACnet Data
ID
COV
Variable Description
DataType
Default
Min
Max
Direction
Analog Value
1
No
Command Output Universal Channel 1
Float
0
0.0
100.0
ReadWrite
Analog Value
2
No
Command Output Universal Channel 2
Float
0
0.0
100.0
ReadWrite
Analog Value
3
No
Command Output Universal Channel 3
Float
0
0.0
100.0
ReadWrite