EN50136 Compliance
35
Installation and programming manual
T2
Terminal “T2” must manage “Hold-up alarm” and “Fault” signals
coming from another two CIE outputs.
Therefore, it is necessary to set up a double-zone balance
connection with EOL (refer to paragraph 4-8-5 Double balanced
zone with EOL) and program terminal T2 as a double zone with the
following zone descriptions:
•
Terminal 02: “Hold-up”
•
Terminal 02D: “Fault”
T3
Terminal “T3” must be connected to the dislodgement-detection
device on the control panel (TamperNO) which in turn must be
connected to a CIE input with normally-closed balance (refer to
paragraph 4-8-1 N.C./N.O. Balancing).
This terminal must be configured as an output associated with the
SmartLinkAdv “open-panel tamper” event.
In this way, dislodgement or open tamper on the SmartLinkAdv will
generate an “SPT Tamper” event in the control panel.
T4
Terminal “T4” must be connected to a CIE input with normally-open
balance (refer to paragraph 4-8-1 N.C./N.O. Balancing).
This terminal must be configured as:
•
normally open output
•
monostable with 5 second monostable time
•
associated with “Unsuccessful call over PSTN” and “Unsuccessful
call over GSM” events
T5
Terminal “T5” must be connected to a CIE input with normally-
closed balance (refer to paragraph 4-8-1 N.C./N.O. Balancing)
This terminal must be configured as:
•
normally-closed output
•
associated with “GSM Fault” and “PSTN line Fault” events
Ty
Tx
Tz
CIE
SmartLink
Adv
Tam
perNO
Swi
tc
h