EN50136 Compliance
Telephone dialler
7-2
Access Levels
The standard defines the following access levels to the device and
distinct limitations of use of the system:
•
Level 1 - access by any person (e.g. passer-by)
•
Level 2 - user access
•
Level 3 - installer or maintenance operator access (authorized
by user - level 2)
•
Level 4 - manufacturer access
7-2-1
Access to level 3
For compliance with standard EN50136-2:2013, an installer or
maintenance person may operate the system with access level 3
only with the authorization of a system user with access level 2.
The procedure to access level 3 is as follows:
1. Disarm the alarm control panel (CIE), if present and connected
to the SmartLinkAdv.
2. Disable the 24h tamper option of the control panel (SmartLiv-
ing control panels must be put in programming mode).
3. Open the SmartLinkAdv.
4. Using the programming cable, connect the PC.
5. Start the SmartLeague software program and open the solu-
tion relating to the system to be accessed.
6. Select SmartLinkAdvanced System from the tree structure,
then go to the Installer Code section underProgramming.
7. Allow the installer to enter the installer code then press Enroll
8. Allow the user to enter the user code, then press OK.
At this point the installer has registered installer access and can
work on the device programming parameters.
7-3
Connection with alarm control panel
(Control and Indicating Equipment)
If the SmartLinkAdv is being used as an SPT (Supervised Premises
Transceiver) for an ATS (Alarm Transmission System), the default
configuration of the terminals must be as illustrated in this
paragraph and must not be changed.
With the exception of what is written in this paragraph, the
configurations shown in paragraphs 4-8 and 4-9 are for
applications in which the SmartLinkAdv is not used as an SPT for an
ATS.
T1
Terminal “T1” must manage “Intrusion Alarm” and “Tamper Alarm”
signals coming from two CIE outputs.
Therefore, it is necessary to set up a double-zone balance
connection with EOL (refer to paragraph 4-8-5 Double balanced
zone with EOL) and program terminal T1 as a double zone with the
following zone descriptions:
•
Terminal 01: “Intrusion”
•
Terminal 01D: “Tamper”