EN50136 Compliance
33
Installation and programming manual
Chapter 7
EN50136 COMPLIANCE
SmartLinkAdv series devices are EN 50136-1 and EN 50136-2
compliant.
The SmartLeague software program provides preset programming
parameters which guarantee 50136-2 standard compliance.
To activate these preset parameters automatically select
Programming, EN50136-2 standard compatibility of the
SmartLinkAdvanced system.
DEFAULT
The default programming of the SmartLinkAdv has:
•
Option “EN50136-2 standard compatibility” enabled
•
Installer code: 999999
•
User code 1: 000001
7-1
ATS Categories
The SmartLinkAdv series devices constitute an SPT (Supervised
Premises Transceiver) which can be used to create an ATS (Alarm
Transmission System) in accordance with the definitions in
standards EN 50136-1 and EN 50136-2.
Note
If the SmartLinkAdv is used as an SPT (Supervised Premises Transceiver) for an
ATS (Alarm Transmission System), it must be powered by the AS (Alarm
System) and not by an IPS12015 power supply which is not allowed.
Table 7-1:
Maximum ATS categories ATS achievable
SPT Model
SPT primary network
interface
ATS categories
Single Path
(SP)
Dual Path
(DP)
SmartLinkAdv/P
PSTN
2
/
SmartLinkAdv/G
GSM/GPRS
6
/
SmartLinkAdv/GP
PSTN
2
2
GSM/GPRS
6
Table 7-2:
ATS Parameters
ATS
Categories
Transmission time
Time
relation
Replacemen
t security
Information
security
Operating
mode
Classification
Maximum
values
Single
Path
2
D2 (60s)
M2 (120s)
T2 (25h)
S0
I0
Pass-through
6
D4 (10s)
M4 (20s)
T6 (20s)
S2
I3
Dual
Path
2
D3 (20s)
M3 (60s)
T3a (30min)
S0
I0
4
D4 (10s)
M4 (20s)
T5 (90s)
S2
I3