5.4. External disconnection device
The AC supply must be shut off for equipment inspection work. To do this, the installer must fit an external
disconnection device.
The switching component must be dimensioned for the DC input voltage and current of the charging terminal (see
section
It must also include the possibility of remote tripping (via minimum coil) that allows it to be opened in case the
charging terminal door is opened accidentally.