ABQ2026IQE01_A - Installation and Operation Manual
Siba
Fuse holder base
size
Fuse size
Rated current
Rated voltage
Without an indicator
With indicator
and adapter for
microswitch
20 243 28,250
20 243 29,250
3L
NH3L
250 A
1500 VDC
20 243 28,315
20 243 29,315
315 A
20 243 28,350
20 243 29,350
350 A
20 243 28,400
20 243 29,400
400 A
20 243 28,450
20 243 29,450
450 A
20 243 28,500
20 243 29,500
500 A
Mersen
Fuse holder base size
Fuse size
Rated current
Rated voltage
HP15NH3LGPV200
3L
3
200 A
1500 VDC
HP15NH3LGPV250
250 A
HP15NH3LGPV315
315 A
HP15NH3LGPV350
350 A
HP15NH3LGPV400
400 A
6.8. Requirements for transformers
6.8.1. Grid connection transformer
CAUTION
These units must be connected to a transformer with the neutral of the low-voltage side isolated, thus
generating an IT grid.
This section lists the technical specifications of the grid connection transformer which converts the medium or
high supply voltage to the operating voltage of the unit.
1. The transformer’s power must be greater than the sum of the power ratings of the connected inverters,
keeping in mind the locations environmental conditions and height.
2.
If connecting the equipment to the transformer's same low voltage winding, these must be synchronized.
These
equipment have all the necessary elements to synchronize up to four inverters.
Low Voltage / Medium
Voltage
INFO
See section
“13. Connection of the DCAC connections module”
to proceed with connection.
48
Preparation for installing the unit
Ingeteam