ABQ2026IQE01_A - Installation and Operation Manual
String13
Current string 13.
String14
Current string 14.
String15
Current string 15.
Total
Energy
Total energy fed through the inverter throughout its useful life.
Time
Total time that the inverter has been feeding the grid.
Connections
Total number of grid connections.
Partial
Energy
Partial energy fed by the inverter.
Time
Partial time that the inverter has been connected to the grid.
Connections
Partial number of grid connections.
Pac
AC power, in watts
Pwatt
Power fed to the public grid in self consumption mode, in watts.
Ratio
Self consumption ratio. Displays the consumption percentage of the loads being fed by the power
generated by the inverter.
19.6.2. Events
This menu shows the events occurring in the inverter.
Alarms
The alarms indicate current events in the inverter that lead to its shut-down.
Alarm
Name
Variable
Code
LED Lighting
Description
Overvoltage
1
0x0001
Orange
This alarm displays when there is an input voltage in the
panel (PV) above the unit's limit.
This voltage is read before the motorized switch,
specifically on the panel input string grouping plates.
Voltage difference
1
0x0002
Orange
The difference between the panel and bus voltage
measurements, both sides of the DC switch, is greater
than the expected limit.
Panel overcurrent
1
0x0004
Red
DC current above the limit allowed by the unit.
AC zero sequence
current
1
0x0008
Red
The instantaneous sum of the AC currents exceeds a
maximum value.
BUS overvoltage
1
0x0010
Red
There is overvoltage exceeding the maximum DC voltage
limit.
Instantaneous AC
overvoltage
1
0x0020
Orange
The instantaneous AC voltage in one of the three phases
exceeds the unit's HW limit.
AC rms voltage or
AC frequency
1
0x0040
0x0200
Orange
The network voltage in one or several phases is outside
of the limits established in the unit's settings for a period
above that defined in the settings. This alarm can be
instantaneous or permanent, depending on the duration
of the fault.
The unit's voltage and frequency relays are configured
according to the limits established in the regulations
applicable to each installation.
Instantaneous AC
overcurrent
1
0x0080
Red
The instantaneous AC current in one of the three phases
exceeds the unit's instantaneous limit.
AC rms overcurrent
1
0x0100
Red
The AC rms current in one of the three phases exceeds
the unit's instantaneous limit.
128
Display control