ABQ2026IQE01_A - Installation and Operation Manual
•
gPV class.
•
Rated current of 50 A
~
500 A, depending on the specifications of the unit.
Fuses of the following sizes and formats are allowed:
Number of inputs
Number of fuses
Fuse holder base size
Maximum size
Recommended size
with I
max
6
6 or 12
(1)
3L
630 A
600 A
7
7 or 14
(1)
3L
630 A
500 A
8
8 or 16
(1)
3L
630 A
400 A
9
9 or 18
(1)
3L
630 A
350 A
10
10 or 20
(1)
3L
630 A
315 A
11
11 or 22
(1)
3L
630 A
315 A
12
12 or 14
(1)
3L
630 A
315 A
13
13 or 26
(1)
2XL
400 A
250 A
14
14 or 28
(1)
2XL
400 A
250 A
15
15 or 30
(1)
2XL
400 A
250 A
(1)
depending on whether it is installed on the positive pole or both poles.
2XL Mechanical specifications
max. 130 mm
max. 174 mm
max. 134 mm
max. 74 mm
max. 61 mm
max. 6 mm
max. 205 mm
46
Preparation for installing the unit
Ingeteam