The certification of a wiring system attests to the quality of the components and the installation. Ingeteam
establishes the certification of the data wiring itself as necessary.
2.5. Operating modes
Below we will briefly explain the operating modes offered by these communications cards.
2.5.1. Ethernet-serial gateway
This mode allows for the firmware update, status view, configuration, history download of the installation’s
inverters, etc. For this, the card listens at port 7128.
2.5.2. Modbus-TCP
Most SCADA systems based on Ethernet communication use the Modbus-TCP protocol as standard. However, the
final communication with Ingeteam inverters is performed by RS-485 using the Modbus-RTU protocol.
In Modbus-TCP mode these cards work as Modbus-TCP and Modbus-RTU protocol translators and also perform
conversion between Ethernet and RS-485 communication media.
The following figure shows the flow of standard communications on a Modbus-TCP request from a SCADA.
Modbus-TCP request to
Node 1
Modbus-TCP response from
Node 1
(1)
(4)
(3)
(2)
Modbus-RTU request to
Node 1
Sending time by RS-485
Processing and response
preparation time
Response time by RS-485
Modbus-RTU response
from Node 1
Modbus-TCP request to
Node 2
Modbus-TCP response from
Node 2
(1)
(4)
(3)
(2)
Modbus-RTU request to
Node 2
Sending time by RS-485
Processing and response
preparation time
Response time by RS-485
Modbus-RTU response
from Node 2
Time out for the
next request
Ethernet
RS-485
Inverters
SCADA
Ethernet card
On the Modbus-TCP mode, the card listens to the requests in port 502 (standard Modbus-TCP). Each request (1)
is converted to Modbus-RTU and is sent through the serial interface (2). Then the unit response (3) is reversed
from Modbus-RTU to Modbus-TCP and is finally sent to the Modbus-TCP client (4).
When designing an Ethernet communications system via the Modbus-TCP protocol, we must keep the following
points in mind.
27
Description of the communication
Ingeteam
AAX2023IQM02_A - User manual
DE
EN
ES
FR
IT
PT
Summary of Contents for AAX0057
Page 1: ...Accessories for local and remote communication User manual...
Page 22: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 40: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 58: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 76: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 94: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 112: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 114: ...Ingeteam Power Technology S A www ingeteam com AAX2023IQM02_A 08 2017...