ALTERNATORS
SERVICING - MAINTENANCE
Ref. 2981 GB - 4.33/a - 04.00
LEROY-SOMER
4.5 - Electrical faults
4.5.1 - Checking the winding
You can check the winding insulation by performing a high
voltage test. In this case, you must disconnect all AVR wires.
Damage caused to the AVR in such conditions is
not covered by our warranty.
Fault
Action
Effect
Check/Cause
No voltage at
no load on
start-up
Connect a new battery
of 4 to 12 volts to
terminals E- and E+,
respecting the polarity,
for 2 to 3 seconds
The alternator builds up and its
voltage is still correct when the
battery is removed.
- Lack of residual magnetism
The alternator builds up but its
voltage does not reach the rated
value when the battery is removed.
- Check the connection of the voltage reference to
the AVR
- Faulty diode
- Armature short-circuit
The alternator builds up but its
voltage disappears when the
battery is removed
- Faulty AVR
- Field windings open circuit (check winding)
- Main field winding open circuit (check the
resistance)
Voltage too
low
Check the drive speed
Correct speed
Check the AVR connections (possible AVR
failure)
- Field windings short-circuited
- Rotating diodes burnt out
- Main field winding short-circuited - Check the
resistance
Speed too low
Increase the drive speed. (Do not touch the AVR
voltage pot. (P2) before running at the correct
speed.)
Voltage too
high
Adjust AVR voltage
potentiometer
Adjustment ineffective
Faulty AVR
Voltage
oscillations
Adjust AVR stability
potentiometer
If no effect : try normal / fast
recovery modes (ST2)
- Check the speed : possibility of cyclic irregularity
- Loose connections
- Faulty AVR
- Speed too low when on load (or LAM set too
high)
Voltage
correct
at no load and
too low when
on load
Run at no load and
check the voltage
between E+ et E- on the
AVR
Voltage between E+ and E- (DC)
AREP / PMG < 10V
- Check the speed (or LAM set too high)
Voltage between E+ and E-
AREP / PMG > 15V
- Faulty rotating diodes
- Short-circuit in the main field. Check the
resistance- Faulty exciter armature. Check the
resistance.
Voltage
disappears
during
operation
Check the AVR, the
surge suppressor, the
rotating diodes, and
replace any defective
components
The voltage does not return to the
rated value.
- Exciter winding open circuit
- Faulty exciter armature
- Faulty AVR
- Main field open circuit or short-circuited
WARNING
Summary of Contents for G 270
Page 2: ......
Page 17: ...Alternator 15...
Page 28: ......
Page 29: ......
Page 30: ......
Page 57: ......
Page 58: ......
Page 121: ......
Page 122: ...7739614 1 English 04 2002...
Page 123: ......
Page 124: ......
Page 125: ...EDITION JUNE2002 CPN 85623031 33519009601 ind1 GENERATOR PARTS LISTS GENERATOR MODEL G270...
Page 151: ...G270 EDITION JUNE2002 27...
Page 184: ......
Page 185: ......
Page 186: ......