Ingersol Rand Dor-O-Matic 77700-900 Installation Instructions Manual Download Page 13

 

77700-084 

Rev. 

     07/02 

    Page 

13

 of 

13

 

75.0073 Nov 01 [Rev 8/8/2002]

 

TROUBLESHOOTING 

 

SENSOR WILL NOT SET-UP UPON INITIAL POWERING 

1.  Check terminal 1 & 2 for proper voltage - 24 Volts AC/DC + 10%. 
2.  Make certain that the field of detection is all clear during the set-up and that all lenses are installed on the sensor. If detection of 

movement is encountered upon initial set-up, the sensor will continuously flash Green at +/- 2 Hz. The sensor will also not set-up if 
permanent stationary objects are extremely close to the sensor.  Ensure that, not only the detection field is clear, but also that the 
sensor is mounted properly.  If the optional mounting block is not used, and the backside of the sensor is less than 3” to the face of 
the door, it may be in saturation due to the door. Install the optional mounting block if necessary. 

3.  Ensure that all wiring connections have been properly made. Refer to wiring diagrams on Page 4,5 and 6. 

 
 

SENSOR WILL NOT SET-UP AFTER PROGRAMMING 

1.  Ensure that no movement is occurring within the field of detection. If the sensor detects movement beyond 20 seconds in its field 

while set-up is taking place, the Green LED will begin flashing at a slower rate of + 1 Hz to indicate an unsuccessful set-up. If this 
occurs, check to ensure that the backside of the sensor is more than 3” to the face of the door, it may be in saturation due to the 
door. If there is adequate distance, increase the angle of detection to 10° and try the set-up again. Make sure that all lenses are in 
place before initiating a set-up. 

2.  If the sensor successfully completes a set-up upon powering, but then will not set-up after programming, reset all parameters to the 

factory default by pressing 

 followed by number 3 or simultaneously pressing PB1 & PB2 at the right side of the sensor (see 

page 11). 

3.  Start the programming procedure over, if successful set-up cannot be obtained thereafter, replace faulty sensor. 

 

DOOR WILL NOT OPEN ONCE SET-UP HAS BEEN COMPLETED 

1.  Check to ensure that there is no detection occurring at the sensor. If the Red LED is on steady, there is detection. Make sure there 

have been no changes in the field of detection since set-up. If permanent changes have occurred, launch a new set-up and re-test 
door. 

2.  Check the setting of the Relay Mode. Relay should be set to Active Mode for most applications. Refer to page 7 “To Inquire About 

A Setting.”   When the relay is in the Active Mode, the relay contacts will be closed when the Red LED is on, and open when the 
Red LED is off. If the relay output, when tested with an Ohm Meter, is closed regardless of the Red Led, and the Relay Mode is set 
to “Active Mode”, replace faulty sensor. 

3.  Disconnect safety wire from door control. Activate door - if door still does not open, the fault lies within the automatic door control, 

not the sensor. If door does open, re-connect wires. 

 

DOOR WILL NOT CLOSE OR SENSOR WILL NOT INHIBIT DURING CLOSING 

1.  If the Red LED is illuminated, launch a new set-up for the “door open” position. If Red LED goes out after Set-Up, walk-test the 

pattern and tune if necessary. 

2.  If Red LED comes back on when door goes open after new set-up, the sensor may not be going into the “door open” pattern. 
3.  Ensure that the wires are connected properly. 

 

GREEN LED FLASHES STEADILY AT A RATE OF+ 2Hz 

If the sensor has tried to launch a new set-up after the expiration of the Automatic Learn Time due to a permanent change in the 
field of detection, and there is continual movement in the field, the sensor will flash the Green Led indefinitely until movement has 
stopped. This may also occur if there is an object that is extremely close to the sensor, thereby causing saturation. Once the object 
or movement has been eliminated, clear the field of detection. The sensor should set-up within 5 seconds and the Green LED 
should go out. Walking in and out of the detection field should cause the Red LED to come on and go out respectively thereafter. 

 

RED LED FLASHES SLOWLY AT A RATE OF + 1 Hz 

1.  Unsuccessful set-up has occurred.  Complete a new set-up according to Quick Reference Guide procedures on Page 2. 

2.  If problem persists, return all parameters to the factory defaults by pressing 

 followed by number 3 or simultaneously pressing 

PB1 & PB2 at the right side of the sensor (page 9). 

3.  Launch a new set-up. If Red LED continues to flash slowly, replace faulty sensor. 
 

RED LED DOES NOT FLASH WHEN UNLOCKING FROM THE REMOTE CONTROL

 

1.  Replace faulty batteries in remote control 
 
2.  If problem persists, the remote control or the sensor may be faulty. If possible, test the remote control on a working sensor.  If 

remote control works, replace faulty sensor.  If not, replace the remote control. At this point set-up may be accomplished according 
to page 10, “Non Remote Set-Up”. 

 

 
DO NOT

 leave any problem unresolved. If you must wait for the following workday to call Dor-O-Matic, leave the door inoperable until 

satisfactory repairs can be made. 

NEVER

 sacrifice the safe operation of the automatic door or gate for an incomplete solution. 

Summary of Contents for Dor-O-Matic 77700-900

Page 1: ...2002 77700 900 Presence Sensor Installation Instructions DOR DOR DOR DOR O O O O MATIC MATIC MATIC MATIC 7350 W Wilson Ave Harwood Heights IL 60706 Toll Free 1 800 543 4635 In Illinois 708 867 7400 S...

Page 2: ...ensor may also be tuned by means of two sensor mounted buttons contained on the PC Board within the unit With these two buttons the sensor s field of detection can be altered without the use of the ha...

Page 3: ...CB within the sensor housing is held in place by two white plastic support clips The clips are notched to allow the PCB to be set at 0 5 and 10 angles with the floor surface If a change in the angle o...

Page 4: ...nal block properly installed at the left side of the sensor terminal 1 will be farthest from the mounting surface and the screws for the terminals will be facing down The terminal block may be pulled...

Page 5: ...77700 084 Rev G 07 02 Page 5 of 13 75 0073 Nov 01 Rev 8 8 2002 WIRING DIAGRAM FOR SENIOR SWING MID SWING CONTROL...

Page 6: ...77700 084 Rev G 07 02 Page 6 of 13 WIRING DIAGRAM FOR ASCENT BENCHMARK PREMIUM CONTROL...

Page 7: ...assistance After the function button is pressed the red LED will flash rapidly 10Hz You will then have 30 seconds to make a numerical choice If a number is not entered within the 30 seconds the senso...

Page 8: ...nly change the parameters that are needed for your application INSTALLATION Position the sensor at the bottom of the header on swing side of the door Utilize the mounting block 87503 600 HMS Spacer wh...

Page 9: ...losed during non detection 2 Active output relay contact closed during detection open during non detection 3 Continuous detection relay contact always closed 4 Continuous non detection relay contact a...

Page 10: ...te the parameter and the green flashes indicate what that particular parameter is set to NOTE Pressing PB1 will toggle between the parameters and pressing PB2 will toggle between the range of adjustme...

Page 11: ...Zone8 Zone9 Zone10 Zone11 Zone12 Zone13 Zone14 Zone15 Zone16 Zone17 Zone18 Zone19 Zone20 Zone21 Zone22 Zone23 Zone24 DOOR DOOR 2 Middle Pattern Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8...

Page 12: ...e5 Zone6 Zone7 Zone8 Zone9 Zone10 Zone11 Zone12 Zone13 Zone14 Zone15 Zone16 Zone17 Zone18 Zone19 Zone20 Zone21 Zone22 Zone23 Zone24 DOOR DOOR Zone1 Zone2 Zone3 Zone4 Zone5 Zone6 Zone7 Zone8 Zone9 Zone...

Page 13: ...ctive Mode the relay contacts will be closed when the Red LED is on and open when the Red LED is off If the relay output when tested with an Ohm Meter is closed regardless of the Red Led and the Relay...

Reviews: