NON-REMOTE SETUP 

 
If you are in the field and do not have a universal remote control, you may set-up the 77700-900 using the manual push buttons (see 
diagram below) located under the right end cap.  Keep in mind, you can only set up the sensitivity, relay mode, pattern width, and 
pattern depth with the manual push buttons.  To set up the sensor without a remote, complete the following: 
 
 
 
 
 
 
 
 
 
 
 
 
 

1. 

To start the set-up process, press PB1 (for less than 2 seconds) 
 

• 

The set-up function will be launched according to the current door position.  The green LED will flash at +/-2 Hz for 10 
seconds.  This LED will stop flashing when you achieve a successful set-up. 

 

• 

If there is an interruption to the field of detection during this procedure, the green LED will flash at a slower rate.  You 
must then press PB1 to launch the set-up again. 

 

2. 

To change the detector’s parameters, press PB1 (for more than 2 seconds), and then release the button. 

 
3. 

Press either PB1 or PB2.  The LED will immediately flash red, followed by a sequence of green flashes.

 

 

4. 

The red flashes indicate the parameter and the green flashes indicate what that particular parameter is set to. 

 

NOTE:

   

Pressing PB1 will toggle between the parameters and pressing PB2 will toggle between the range of adjustments for that 

particular setting.  Once you achieve the highest adjustment, you will go back to the lowest setting by pressing PB2.  For example, a 
value of zero (0) will not flash green; a value of one (1) will flash green one time. 

 

5. 

To exit manual set-up, simply wait 20 seconds or press PB1 for more than 2 seconds.  Place the right end cap back 
on the sensor. 

 

RED LED STATUS 

PARAMETER 

SYMBOL 

DESCRIPTION 

GREEN LED STATUS 

1 Red Flash 

 

Sensitivity (Door open) 

0 – 9 Green Flashes (default = 8) 

2 Red Flashes 

 

Sensitivity (Door closed) 

0 – 9 Green Flashes (default = 8) 

3 Red Flashes 

 

Relay Mode 

1 – 4 Green Flashes (default = 1) 

4 Red Flashes 

 

Auto Learn Time 

0 – 9 Green Flashes (default = 0) 

5 Red Flashes 

Pattern Width (Door Open)  

0 – 9 Green Flashes (default = 2) 

6 Red Flashes 

Pattern Width (Door Closed) 

0 – 9 Green Flashes (default = 1) 

7 Red Flashes 

 

Pattern Depth (Door Open) 

1 – 3 Green Flashes (default = 1) 

8 Red Flashes 

 

Pattern Depth (Door Closed) 

1 – 3 Green Flashes (default = 1) 

 

ONCE THE SET-UP PHASE IS COMPLETE (MANUAL OR REMOTE), WALK TEST THE FIELD OF DETECTION TO 

ENSURE ADEQUATE COVERAGE AND COMPLIANCE WITH ANSI STANDARDS. 

PB1 

PB2 

Summary of Contents for Dor-O-Matic 77700-900

Page 1: ...2002 77700 900 Presence Sensor Installation Instructions DOR DOR DOR DOR O O O O MATIC MATIC MATIC MATIC 7350 W Wilson Ave Harwood Heights IL 60706 Toll Free 1 800 543 4635 In Illinois 708 867 7400 S...

Page 2: ...ensor may also be tuned by means of two sensor mounted buttons contained on the PC Board within the unit With these two buttons the sensor s field of detection can be altered without the use of the ha...

Page 3: ...CB within the sensor housing is held in place by two white plastic support clips The clips are notched to allow the PCB to be set at 0 5 and 10 angles with the floor surface If a change in the angle o...

Page 4: ...nal block properly installed at the left side of the sensor terminal 1 will be farthest from the mounting surface and the screws for the terminals will be facing down The terminal block may be pulled...

Page 5: ...77700 084 Rev G 07 02 Page 5 of 13 75 0073 Nov 01 Rev 8 8 2002 WIRING DIAGRAM FOR SENIOR SWING MID SWING CONTROL...

Page 6: ...77700 084 Rev G 07 02 Page 6 of 13 WIRING DIAGRAM FOR ASCENT BENCHMARK PREMIUM CONTROL...

Page 7: ...assistance After the function button is pressed the red LED will flash rapidly 10Hz You will then have 30 seconds to make a numerical choice If a number is not entered within the 30 seconds the senso...

Page 8: ...nly change the parameters that are needed for your application INSTALLATION Position the sensor at the bottom of the header on swing side of the door Utilize the mounting block 87503 600 HMS Spacer wh...

Page 9: ...losed during non detection 2 Active output relay contact closed during detection open during non detection 3 Continuous detection relay contact always closed 4 Continuous non detection relay contact a...

Page 10: ...te the parameter and the green flashes indicate what that particular parameter is set to NOTE Pressing PB1 will toggle between the parameters and pressing PB2 will toggle between the range of adjustme...

Page 11: ...Zone8 Zone9 Zone10 Zone11 Zone12 Zone13 Zone14 Zone15 Zone16 Zone17 Zone18 Zone19 Zone20 Zone21 Zone22 Zone23 Zone24 DOOR DOOR 2 Middle Pattern Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8...

Page 12: ...e5 Zone6 Zone7 Zone8 Zone9 Zone10 Zone11 Zone12 Zone13 Zone14 Zone15 Zone16 Zone17 Zone18 Zone19 Zone20 Zone21 Zone22 Zone23 Zone24 DOOR DOOR Zone1 Zone2 Zone3 Zone4 Zone5 Zone6 Zone7 Zone8 Zone9 Zone...

Page 13: ...ctive Mode the relay contacts will be closed when the Red LED is on and open when the Red LED is off If the relay output when tested with an Ohm Meter is closed regardless of the Red Led and the Relay...

Reviews: