ABB2000IKI01
68
Installation manual
Ingeteam
Screen 5
Rpv
Impedance of the entire PV array to ground.
Rpv+
Impedance of the positive pole of the PV array to ground.
Rpv-
Impedance of the negative pole of the PV array to ground.
Screen 6
Alarms
Status of inverter alarms.
0000H
No alarms.
0001H
Grid frequency out of range.
0002H
Grid voltage out of range.
0004H
PI current saturation.
0008H
Unexpected reset.
0010H
Continuous overload at output.
0020H
Temperature alarm in the power electronics.
0040H
Hardware fault. Synchronization fault.
0080H
Instantaneous overload at output.
0100H
AC circuit protection.
0200H
DC circuit protection.
0400H
Insulation fault.
0800H
Power electronics fault.
1000H
Manual shutdown alarm.
2000H
Configuration change alarm.
4000H
Panel input overvoltage.
8000H
Low voltage in the PV array.
Alarmas Hist
Alarms since the last connection. This value is reset each time the inverter is connected to the grid. It
has the same code as the “alarms” variable.
TempInt
Inverter power electronics temperature.
TempCI
Inverter control electronics temperature.
Screen 7
Conn.N
Number of grid connections made during all hours of operation.
ParConn.N
Number of grid connections since counter was last reset.
ConnT
Number of hours the inverter has been connected to the grid.
Par.ConnT
Number of hours the inverter has been connected to the grid since the counter was last
reset.
8.5. Reasons for shutdown
This menu shows the last five inverter shutdowns, with reasons and corresponding date and time.
17:05
24/06/12
17:05
24/06/12
Meaning of reasons for shutdown: