Parameter 2:
Select “
Add
” or “
Sub
” function to
calibrate battery voltage to real figure.
Parameter 3:
The voltage setting range is from
0V to 5.7V. The default value is 0V.
14: reserved
Interface
Setting
reserved
15: Inverter voltage calibration
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to
calibrate inverter voltage
Parameter 3:
The voltage setting range is from
0V to 6.4V. The default value is 0V.
16: Floating charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to
adjust floating charger voltage.
Parameter 3:
the voltage range is from
0V to
6.4V
, the default value is 0V.
17: Constant charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to
adjust constant charger voltage.
Parameter 3:
the voltage range is from
0V to
3.2V
, the default value is 0V.
18: Maximum charger current setting