4) Remove the cabinet cover, and then modify the jumpers (CN1) on the control board
to set the battery numbers as following table:
Battery
Number
CN1
pin15
Pin16
Pin17
Pin18
Pin19
Pin20
16
X
1
0
0
0
0
17
X
0
1
0
0
0
18
X
0
0
1
0
0
19
X
0
0
0
1
0
20
X
0
0
0
0
1
Note
:
1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.
5) Modify the battery pack for the setting number carefully. After complete it, put the
cover back, and switch on the battery breaker for long-run model.
6) Switch on the input breaker and the UPS will enter Bypass mode.
3-5. Meaning of the abbreviations on the LCD Display
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ATO
Auto
BAT
Battery
NCF
Normal mode (not CVCF mode)
CF
CVCF mode (frequency converter
mode)
SUB
Subtract
ADD
Add
ON
On
OFF
Off
FBD
Not allowed
OPN
Allow
RES
Reserved