06: reserved
Interface
Setting
reserved
07: reserved
Interface
Setting
reserved
08: Bypass mode setting
Interface
Setting
Parameter 2:
OPN
: Bypass allowed. W hen selected, UPS will
run at Bypass mode depending on bypass
enabled/disabled setting.
FBD
: Bypass not allowed. When selected, it’s
not allowed for running in Bypass mode under
any situations.
Parameter 3:
ENA
: Bypass enabled. W hen selected, Bypass
mode is activated.
DIS
: Bypass disabled. W hen selected, automatic
bypass is acceptable, but manual bypass is not
allowed. Manual bypass means users manually
operate UPS for Bypass mode. For example,
pressing OFF button in AC mode to turn into
Bypass mode.