INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line
– Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - [email protected] – 11 17 AA 59 204 18
19
2) Charging batteries for at least 10 hours before use is recommended. Otherwise,
the backup time may be shorter than expected.
3) Make sure the battery numbers setting on the control panel (Please refer to the
section 3-4-11 for detailed settings) complies with the actual connection.
4) The charging current can be changed from 1A to 6A through the LCD panel or the
sowftare. Please make sure that the charging current meets the batteries
requirements.
5. Battery mode operation
1) When the UPS is in Battery mode, the buzzer will beep according to different
battery capacites. If the battery capacity is more than 25%
,
the buzzer will beep
once every 4 seconds; If the battery voltage drops to the alarm level, the buzzer
will beep quickly (once every sec) to remind users that the battery is at a low level
and that the UPS is about to automatically shut down. Users can switch off some
non-critical loads to disable the shutdown alarm and prolong the backup time. If
there is no more load to be switched off, you have to shut down all loads as soon
as possible to protect the devices from load failure and/or data loss.
2) In Battery mode, users can press the Mute button to disable the buzzing sound.
3) The backup time of the long-run
model depends on the external batteries’
capacity.
4) The backup time may vary with different environment temperatures and load
types.
5)
When setting backup time for 16.5 hours (default value from LCD panel), after
discharging 16.5 hours, UPS will shut down automatically to protect the battery.
This battery discharge protection can be enabled or disabled using the LCD panel
control. (Refer to 3-7 LCD setting section)
6. Turn off the UPS with the utility power supply in AC mode
1) Turn off the UPS inverter by pressing the
“OFF” button for at least 1s. The buzzer
will beep once and the UPS will switch to Bypass mode.
NOTE 1:
If the UPS has been set to enable the bypass output, it will bypass
voltage from the utility power to the output sockets and terminal even though the
UPS is switched off (inverter).