Inverter voltage Calibration
Y
Y
Y
16
Floating charger voltage
adjustment
Y
Y
Y
Y
Y
17
Constant charger voltage
adjustment
Y
Y
Y
Y
Y
18
Charger maximum current setting
Y
Y
Y
Y
Y
19
Battery capacity and groups
setting
Y
Y
Y
Y
Y
20
Backup time calibration
Y
Y
Y
Y
Y
*Y (YES) means that this program can be set in this mode.
01: Output voltage
Interface
Setting
Parameter 3: Output voltage
You may choose the following output voltage in
parameter 3:
208:
Presents output voltage is 208Vac
220:
Presents output voltage is 220Vac
230:
Presents output voltage is 230Vac
240:
Presents output voltage is 240Vac
02: Output frequency
Interface
Setting
60 Hz, CVCF mode
50 Hz, Normal mode
ATO
Parameter 2: Output Frequency
Setting the output frequency. You may choose
following three options in parameter 2:
50.0Hz:
The output frequency is setting for
50.0Hz.
60.0Hz:
The output frequency is setting for
60.0Hz.
ATO:
If selected, output frequency will be
decided according to the latest normal utility
frequency. If it is from 46Hz to 54Hz, the output
frequency will be 50.0Hz. If it is from 56Hz to
64Hz, the output frequency will be 60.0Hz. ATO
is default setting.
Parameter 3: Frequency mode
Setting output frequency at CVCF mode or non-
CVCF mode. You may choose following two
options in parameter 3:
CF:
Setting UPS to CVCF mode. If selected, the
output frequency will be fixed at 50Hz or 60Hz
according to setting in parameter 2. The input