BF
Battery Fault
BR
Battery Replacement
EE
EEPROM error
3.5 UPS setting
There are three parameters to set
up the UPS.
Parameter 1: It’s for program
alternatives. Refer to below table.
Parameter 2 and parameter 3 are
the setting options or values for
each program
01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage
For 120Vac models, you may choose the following output voltage:
100:
presents output voltage is 100Vac
110:
presents output voltage is 110Vac
115:
presents output voltage is 115Vac
120:
presents output voltage is 120Vac (Default)
125: presents output voltage is 125Vac
For 230Vac models, you may choose the following output voltage:
200:
presents output voltage is 200Vac
208:
presents output voltage is 208Vac
220:
presents output voltage is 220Vac
230:
presents output voltage is 230Vac (Default)
240:
presents output voltage is 240Vac
02: Programmable outlets enable/disable
Interface
Setting
Parameter 2:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
Parameters 1
Parameters
2 & 3