INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - [email protected] – 12 18 AA 59 205 19
36
NOTE: When installing the UPS or battery pack with feet, please keep 70mm distance from
the edge of the unit.
2.4 Setup the UPS
Step 1 - UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using
extension cords.
Model
Wiring spec (AWG) mm²/AWG
Input
Output
Ground
E3
Performance
5000 RT
6mm²/AWG12
6mm²/AWG12 for
terminal
1.5mm²/AWG16 for
10/16A Sockets
6mm²/AWG12 for
terminal
1.5mm²/AWG16 for
10/16A Sockets
Wiring specs
Terminal block wiring diagram
Step 2 - UPS output connection
For socket-type outputs, there are an output terminal block for connection of the load via a
distribution board and two kinds of outputs: programmable outlets and general outlets.
Please connect non-critical devices to the programmable outlets and critical devices to the
general outlets. During power failure, you may extend the backup time to critical devices by
setting shorter backup time for non-critical devices.
INPUT
OUTPUT