System Description 

DC Power Supply Operation Mode 

If  the  equipment  is  being  ordered  as  DC  Power  Supply,  then  the  unit  supplies  a  limited  voltage  and 
current  value  that  is  adjusted  from  the  front  panel  to  the  connected  DC  load.  The  output  voltage  and 
current limits can be easily adjusted separately from the SETTINGS menu on the LCD panel.  

Battery Charger Operation Mode 

The  equipment  that  is  ordered  as  battery  charger  has  the  following  specifications. This  operation  mode 
has 4 graduated charging level depending on the battery type. These are initial charge, float charge, boost 
charge  and  temperature  or  auto  controlled  charging  types.  The  charge  voltages  per  cell  ;                              
for  initial  charge:  2.04V,  for  float  charge:  2.23V,    for  boost  charge:  2.375V,  for  temperature  controlled 
charge ;  2.17V at 0

0

C / 2.29V at 50

0

C. These are factory set values, and temperature controlled values can 

be set from front panel according to the battery type.  

LVD ( Low Voltage Disconnector ) can be included to the unit as an option. This function protects the 
batteries from deep discharge by disconnecting them from output during battery mode when the mains is 
absent.  

Additionally, the dry contact alarm card is an optional feature with its automation functionality. 

 

 

 

                                                            SYSTEM BLOCK  DIAGRAM 

 

 

 

 

 

Summary of Contents for Infocharger

Page 1: ...Infocharger DC POWER SUPPLY BATTERY CHARGER...

Page 2: ...tions For the staff and equipment safety it is necessary for the users to fully read and save this manual before working on this equipment Description of the Symbols IMPORTANT NOTICE Please follow the...

Page 3: ...connection 5 4 Switch On and Switch OFF procedures 6 4th1 System Switch ON 6 4th2 System Switch OFF 6 5 Operating Instructions 7 5th1 Unit Operation 7 5th1 1 Operation modes 7 5th2 Displays 8 5th2 1...

Page 4: ......

Page 5: ...missioning have to be done by authorized technical service Earth Ground connection should be done Do not plug in off the communication interface cables during bad weather conditions with lightning To...

Page 6: ...ing on the battery type These are initial charge float charge boost charge and temperature or auto controlled charging types The charge voltages per cell for initial charge 2 04V for float charge 2 23...

Page 7: ...Battery Charger features and benefits Feature Benefit PWM technology Transformerless design Compact design small dimensions and low weight Microprocessor controller To use all the sources in optimum...

Page 8: ...3rd1 Handling If needed to move the battery charger it is obligatory to pack the unit It is suggested to keep the original packing 3rd2 Storage Please store the battery charger in an environment wher...

Page 9: ...onnection between the grounding unit of the Infocharger and the ground can be made according to the minimum cross sectioned cables which are given in the technical specifications table below 3rd4 2 In...

Page 10: ...he automatic fuses on the front panel if mains voltage is within the limits the unit switches on Inforcharger makes self test for few seconds to check if everything is normal and then starts to charge...

Page 11: ...25 30 35 1 6 11 16 21 26 31 36 41 46 51 TIME CURRENT VOLTAGE 0 0 5 1 1 5 2 2 5 Ibat Vbat Cell Battery current is controlled in a way to keep stable the power transferred to batteries in direct charge...

Page 12: ...our display sections on the control panel as follows On the Operation mode section of the display the actual operating mode is seen On the left part of this display section the following messages can...

Page 13: ...the output voltage is adjustable between values 0 30 0 60 0 140 VDC Iout It is adjustable between 0 255 the current is adjustable between values 0 60 0 30 0 15 A according to the type of Infocharger I...

Page 14: ...ress between 0 8 Ver Seri no Serial number 5th2 1 2 Buttons There are mainly four buttons in the front panel The functionalities of the buttons are given below button Scroll down to next line button S...

Page 15: ...n be chosen on the control panel This voltage level can not be less than 1 65V which is the minimum voltage level per cell 2 Delay module This module is designed for the automation processes and has 8...

Page 16: ...n the unit than you should perform the following Disconnect the loads Bring all the fuses on the unit to 0 position Clean the unit with a slightly moistened cloth Do not drop any liquid and solid fore...

Page 17: ...se check input fuses If you can read the battery and load voltage on front panel but can not measure the same voltage at battery and load then check the battery and load fuses If there is an over temp...

Page 18: ...running 90 280 V Input frequency range at mains running 45 Hz 65 Hz Power factor at nominal input voltage 0 99 Current Total Harmonic Distortion THD 3 Efficiency 90 Output Output voltage 24VDC 48VDC...

Page 19: ...e range at mains running 176 265 V Input frequency range at mains running 45 Hz 65 Hz Power factor at nominal input voltage 0 8 Efficiency 90 OUTPUT Output voltage 24VDC 48VDC 110VDC 220VDC Initial ch...

Page 20: ...Cable cross section area mm2 Current value absorbed by t he load Amp 1 5 18 4 34 6 44 10 61 16 82 25 108 35 135 50 168 70 207 95 250 120 292 150 335 185 382 240 453 300 504 THESE UNITS ARE GIVEN FOR...

Page 21: ...I TAFICS RCU ddb BLOCK DIAGRAM 1 1 CHARGE RECTIFIER INF561 Y18 S101 1 00 MAIN CONTROL BOARD DISPLAY DRIVER SUP CONTROL RELAY X4 X403 X404 FAN X101 X101 X401 X403 X101 X102 X103 X205 X206 L L X1 X2 X3...

Reviews: