INFOCHARGER
9
On the “Status mode” section of the display, if the unit is on-line or fault status. On the right part of this
display section the following messages can be observed:
OK : It is observed when the unit is online-
FAULT : It is observed the unit is out of function-
MENU STRUCTURE
1-Analog values
Vbatt : Battery voltage
Ibatt : Battery current
Vload : Load voltage
Iload : Load current
Vinput : Input voltage
Tred : Internal temperature of the charger
Ifan : Fan current
Tenv: Environmental(ambient) temperature
2-Adjustments
Operational mode as DC or CH: DC power supply or CH battery charger
If DC mode is selected-(DC power supply)
Vout :It is adjustable between 0 –255, the output voltage is adjustable
between values 0-30, 0-60, 0-140 VDC .
Iout : It is adjustable between 0-255, the current is adjustable between
values 0-60, 0-30, 0-15 A according to the type of Infocharger.
If CH mode is selected -(Battery charger)
Battery capacity: It is between 0-1000 Ah
Charge current: It is adjustable between 0-100%
Low voltage protection: It is adjustable between 19-22, 38-44 , 85-100VDC
Temperature controlled charging = PRESENT OR NOT
0
°°°°
C volt VALUE: Adjustable depending on the type (battery charging voltage at 0
°°°°
C )
50
°°°°
C volt VALUE: different depending on type(battery charging voltage at 0
°°°°
C )
Max. charging time: 0-10 hours
Low voltage limit: LVD low voltage limit DC-
3- ALARMS
Vinput: In case of the voltage at mains is out of limit value
Vbatt : In case of the battery current is out of limit value
Vload : In case of the load voltage is out of limit value
Summary of Contents for Infocharger