Man-1078_Sigma_CP_AUS_12
Page 19 of 29
CODE FUNCTION
COMMENTS
71*
ZONE 1 SHORT CIRCUIT INDICATES ALARM
Changes the trigger threshold of the zone so that the control
panel can be used on older systems that had no short-circuit
monitoring.
72*
ZONE 2 SHORT CIRCUIT INDICATES ALARM
73*
ZONE 3 SHORT CIRCUIT INDICATES ALARM
74*
ZONE 4 SHORT CIRCUIT INDICATES ALARM
75*
ZONE 5 SHORT CIRCUIT INDICATES ALARM
76*
ZONE 6 SHORT CIRCUIT INDICATES ALARM
77*
ZONE 7 SHORT CIRCUIT INDICATES ALARM
78*
ZONE 8 SHORT CIRCUIT INDICATES ALARM
81*
ZONE 1 NON-LATCHING
Renders the zone self-resetting so that it can be used to receive
signals from other systems and will reset when the input is
removed.
Note: It can take up to 20 seconds for zone to reset itself when
sounders are operating
82*
ZONE 2 NON-LATCHING
83*
ZONE 3 NON-LATCHING
84*
ZONE 4 NON-LATCHING
85*
ZONE 5 NON-LATCHING
86*
ZONE 6 NON-LATCHING
87*
ZONE 7 NON-LATCHING
88*
ZONE 8 NON-LATCHING
91
ZONE 1 DOES NOT SOUND ALARMS
Prevents the zone from operating the two common sounder
outputs.
92
ZONE 2 DOES NOT SOUND ALARMS
93
ZONE 3 DOES NOT SOUND ALARMS
94
ZONE 4 DOES NOT SOUND ALARMS
95
ZONE 5 DOES NOT SOUND ALARMS
96
ZONE 6 DOES NOT SOUND ALARMS
97
ZONE 7 DOES NOT SOUND ALARMS
98
ZONE 8 DOES NOT SOUND ALARMS
A1*
ZONE 1 ANY ALARM DELAYED
Zone needs to be triggered for 30 seconds continuously before
an alarm is generated.
A2*
ZONE 2 ANY ALARM DELAYED
A3*
ZONE 3 ANY ALARM DELAYED
A4*
ZONE 4 ANY ALARM DELAYED
A5*
ZONE 5 ANY ALARM DELAYED
A6*
ZONE 6 ANY ALARM DELAYED
A7*
ZONE 7 ANY ALARM DELAYED
A8*
ZONE 8 ANY ALARM DELAYED
C1
ZONE 1 SOUNDERS INHIBITED
Enables individual zones to be configured not to operate zonal
sounders.
On 2 wire “T” series panels this enables individual zones to be
configured for use with conventional (non 2-wire) detector
bases.
C2
ZONE 2 SOUNDERS INHIBITED
C3
ZONE 3 SOUNDERS INHIBITED
C4
ZONE 4 SOUNDERS INHIBITED
C5
ZONE 5 SOUNDERS INHIBITED
C6
ZONE 6 SOUNDERS INHIBITED
C7
ZONE 7 SOUNDERS INHIBITED
C8
ZONE 8 SOUNDERS INHIBITED
E1*
ZONE 1 WILL NOT OPERATE FIRE RELAY
Enables individual zones to be selected to not operate the fire
relay. This is sometimes combined with the non-latching
function to prevent ring around on interconnected panels.
E2*
ZONE 2 WILL NOT OPERATE FIRE RELAY
E3*
ZONE 3 WILL NOT OPERATE FIRE RELAY
E4*
ZONE 4 WILL NOT OPERATE FIRE RELAY
E5*
ZONE 5 WILL NOT OPERATE FIRE RELAY
E6*
ZONE 6 WILL NOT OPERATE FIRE RELAY
E7*
ZONE 7 WILL NOT OPERATE FIRE RELAY
E8*
ZONE 8 WILL NOT OPERATE FIRE RELAY
NOTE: Setting the options marked with asterisks does not comply with AS7240-2
Once the required configuration options have been set, the
Write Enable
switch
must
be returned to its
normal position to the left. The
General Fault
indicator will remain lit if the
Write Enable
switch is not turned
OFF.
18
Watchdog reset switch
If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will
attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate
these events.
If a watchdog event occurs, the control panel will show the
Fault
and
System Fault
less on the front panel,
the
CPU Fault
ed inside the panel.