background image

Man-1078_Sigma_CP_AUS_12 
 

Page 15 of 29

 

16

 

Panel operation 

 

16.1

 

Normal condition 

Under normal conditions, control panels will have only the green, 

Power On

 LED lit.   

 

16.2

 

Fire condition 

Upon receipt of a fire condition by activation of a detector or call point, the 

Common Fire

 indicator will light 

and the

 Fire in Zone

 indicators will flash at around 2Hz. 

The 

Fire

 and 

Local Fire

 relays will also operate and signal any systems to which they are connected. 

Any sounders connected to the sounder circuits will operate in common, zonal or 2-stage mode as selected 
by configuration options 10 to 12 (see Table

 8

). 

 

16.3

 

Silence/Sound Alarms 

The 

Silence/Sound  alarm

  button  can  only  be  operated  at  access  level  two  which  means  that  the 

Enable 

Control

 keyswitch must be activated.   

To silence the sounders, activate the 

Enable Control

 keyswitch and press the 

Silence/Sound Alarm

 button.   

When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state. 
Pressing the 

Silence/Sound Alarm

 whilst the control panel is in this silenced condition will cause the sounders 

to operate again. 
The sounders can be toggled on and off with the 

Silence/Sound Alarm

 button as required. 

 

16.4

 

Reset 

To reset the panel, activate the 

Enable Control

 keyswitch then press the 

Reset

 button. 

 

16.5

 

Zone fault 

Removal of a detector from its base or a fault on any of the zone wiring will cause the 

Fault

 LED and 

Zone 

Fault

 LEDs to light indicating the zone in which the fault has occurred.  Zone fault is non-latching and will 

automatically reset once the fault has been rectified. 
 

16.6

 

Sounder fault 

A fault on the wiring to sounder circuits will cause the 

Fau

lt and 

Sounder Fault

 LEDs to light indicating a fault 

on  the  wiring  to  the  sounder  circuits.    Sounder  fault  is  non-latching  and  will  automatically  reset  once  the 
fault has been rectified. 

 

16.7

 

Power fault 

Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit 
will  cause  the 

Fault 

and 

Power  Fault

  LEDs  to  light  indicating  an  abnormality  in  the  power  supply  to  the 

control panel.  Power fault is non-latching and will automatically reset once the fault has been rectified. 
 

16.8

 

System fault 

The 

System  Fault

  LED  will  light  if  the  configuration  memory  has  not  been  set  or  has  become  corrupt.  

System fault is non-latching and will automatically reset once the configuration has been rectified. 
 

16.9

 

Lamp test 

All  LED  indicators  can  be  tested  at  any  time  by  pressing  the 

Lamp  Test

  button.    The 

Enable  Control

 

keyswitch does not need to be activated to test the indicators. 
 

16.10

 

Buzzer Silence 

The  buzzer  can  be  silenced  at  any  time  by  pressing  the 

Alarm/Fault  Warning  Silence

  button.    The 

Enable 

Control

 keyswitch does not need to be activated to silence the buzzer. 

 

Summary of Contents for Sigma CP

Page 1: ...SIGMA CP Issue 1 November 2011 Conventional Fire Control Panel AFP 2516 Operation and Maintenance Manual ...

Page 2: ... remote control terminals 13 13 Aux 24V DC supply 14 14 Connection to relay contacts 14 15 Connection to Accessory modules 14 16 Panel operation 15 16 1 Normal condition 15 16 2 Fire condition 15 16 3 Silence Sound Alarms 15 16 4 Reset 15 16 5 Zone fault 15 16 6 Sounder fault 15 16 7 Power fault 15 16 8 System fault 15 16 9 Lamp test 15 16 10 Buzzer Silence 15 16 11 Disablements 16 16 12 Disable z...

Page 3: ...e fault 20 20 8 S1 fault and S2 fault 20 20 9 Comms fault 21 21 AIM Australian Interface Module 21 21 1 ACF Ancillary Control Function 22 21 1 1 Outputs 22 21 1 2 Configuration 22 21 1 3 Controls only available at Level 2 22 21 2 Door Holder Output 23 21 3 ASE Outputs Alarm Signalling Equipment 23 21 4 Installation 23 21 5 Configuration 23 22 Power supply 24 23 Maintenance 25 24 Zone designation l...

Page 4: ...s ensure that configuration mode 25 is not set To disable sounders on individual detector circuits set configuration mode 25 and disable individual circuits through the setting of C1 to C8 See Section 17Table 8 DETECTOR BASES WILL BE DAMAGED IF THE INCORRECT MODEL IS USED ON CIRCUITS WHICH HAVE SOUNDERS ENABLED DAMAGE DUE TO INCORRECT CONFIGURATION WILL NOT COVERED UNDER WARRANTY ...

Page 5: ...will be safe and without risk to health when properly used An article is not regarded as properly used if it is used without regard to any relevant information or advice relating to its use made available by the supplier This product should be installed commissioned and maintained by trained service personnel in accordance with the following i Local regulations for electrical equipment in building...

Page 6: ... an accessible position as agreed with the end user Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not liable to move once fixed The control panel should not be mounted in another enclosure or near sources of excessive heat Cables should be connected using suitable cable glands fitted to the knockouts provided If additional cable entry p...

Page 7: ...ngs not to be exceeded Local fire relay contact rating 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Zone quiescent current 1 6mA maximum See Table 4for detector types Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire Number of detectors per zone 20 Dependent on type Number of sounders per circuit Dependent on type and current consumption See Table 6for sounder types Det...

Page 8: ...ts YBN R 4C PLAIN BASE HOCHIKI YBO R 4A LED BASE HOCHIKI YBO R 6PA LED BASE HOCHIKI MUS1A R470SG 01 CALL POINT KAC MUS1A R470SF 01 CALL POINT KAC Table 6 Compatible sounders Model Type Manufacturer Comments ROSHNI FULLEON SQUASHNI FULLEON SQUASHNI MICRO FULLEON Table 7 Compatible I S barriers Note To use detectors and sounders within an intrinsically safe area the detectors and sounders must be of...

Page 9: ...ected to a zone is limited by the I S approval system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified on the system diagram Figure 1 Detection zone wiring through an MTL5061 I S barrier SOUNDER OUTPUT I S POLARISED SOUNDER 10K END OF LINE RESISTOR MTL778...

Page 10: ...LECT and ENTER buttons are provided to allow easy entry and storage of codes to configure the control panel to suit the requirements of the installation Opening the fascia The fascia of the control panel is held in place by a screw on the right hand side Undo the screw and lift the plate from the right hand side Opening the fascia allows more room when mounting the cabinet and fitting cables ...

Page 11: ...in processor by removing the plate holding the PCB from the enclosure and turning it over The software version will have a number such as Sig27 hex and it is this number which will determine which features the panel has installed and its compatibility with Sigma CP ancillary board sounders boards repeaters etc CORRECT INCORRECT INCORRECT SW1 SW2 SW4 SERIAL NUMBER D 1008 ISSUE06 C 1 R 1 R2 R3 R5 R6...

Page 12: ...istors that are factory fitted to the control panel s terminals must be removed and placed across the last device that is wired to the zone circuit Wiring can be conventional using standard detector bases K series or by the use of special detector bases it is possible to wire the system such that detection devices and sounders are fitted to the same pair of wires T series Detection zone circuits m...

Page 13: ...m load of 0 41 Amps on any one circuit 12 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted by an access level 2 control as defined in AS7240 2 These are abbreviated at the terminals block as follows a Remote 0V supply R0V b Silence Alarm SIL c Sound Alarm AL d Fault FLT e ...

Page 14: ...ctivation of a fire condition on any of the zones or pressing of the Sound Alarm Button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not operate upon activation of the remote AL input or when a fire condition is triggered on a zone that is in test mode Fire relay The fire relay will energise upon activation of a fire condition...

Page 15: ...button 16 5 Zone fault Removal of a detector from its base or a fault on any of the zone wiring will cause the Fault LED and Zone Fault LEDs to light indicating the zone in which the fault has occurred Zone fault is non latching and will automatically reset once the fault has been rectified 16 6 Sounder fault A fault on the wiring to sounder circuits will cause the Fault and Sounder Fault LEDs to ...

Page 16: ...tion 22 16 16 Test mode Fire alarm systems must be tested regularly to ensure that they are functioning correctly The Sigma CP range of panels enable the system to be tested single handed by using a test mode When in test mode activation of a fire alarm will be automatically reset after a few seconds to eliminate the need to return to the control panel to reset after every activation Test mode is ...

Page 17: ...played pressing the Enter button will cause the dot on the units seven segment display to flash This indicates that a configuration option has been set To review which configuration options have been set previously simply scroll through numbers 1 to 99 A1 to A8 C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set DOT FLASHING NO DOT ZONE 1 I S BARRIER OPTION SET...

Page 18: ...ector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 31 ZONE 1 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0 9 when selected zone s triggered by detector only Note Access level 2 function Ad must be set for this to t...

Page 19: ... 6 ANY ALARM DELAYED A7 ZONE 7 ANY ALARM DELAYED A8 ZONE 8 ANY ALARM DELAYED C1 ZONE 1 SOUNDERS INHIBITED Enables individual zones to be configured not to operate zonal sounders On 2 wire T series panels this enables individual zones to be configured for use with conventional non 2 wire detector bases C2 ZONE 2 SOUNDERS INHIBITED C3 ZONE 3 SOUNDERS INHIBITED C4 ZONE 4 SOUNDERS INHIBITED C5 ZONE 5 ...

Page 20: ...ked together Test the battery Disconnect the battery and ensure that 28 Volts can be measured on battery charger leads 20 3 CPU fault Indicates that the central processor unit has failed to correctly execute code and has been re started by the system watchdog The Watchdog Reset switch must be pressed to clear the CPU Fault condition If system does not return to normal after the Watchdog Reset swit...

Page 21: ...or comms fault at all repeaters and ancillary boards to identify the source of the problem 21 AIM Australian Interface Module The AIM module is optional on the Sigma range of panels and can be utilised to provide ACF Output Door Holder Output ASE Outputs Only one AIM is permitted on each control panel and has a fixed addressed at o7 output unit 7 ...

Page 22: ... output is active A fault on the ACF outputs is signalled at the Sigma panels as a General fault and on the AIM as ACF fault 21 1 2 Configuration The ACF can be configured as latching by setting the LATCH dipswitch to the On position The ACF can be configured as failsafe Normally Energised by setting the FAIL S dipswitch to the ON position 21 1 3 Controls only available at Level 2 When the ACF is ...

Page 23: ...t relay outputs rated at 30VDC 1Amp are provided to facilitate connection of the Sigma fire panel to a variety of ASE depending on the installation It is the responsibility of the installer to ensure that the ASE being installed is compatible with the local fire station to which it is being connected ALARM normally de energisedactivates on a non disabled Alarm FAULT normally de energisedactivates ...

Page 24: ...ether close to the mains terminal block with a cable tie The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see Table 2 for battery size required for each model The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps Battery leads are supplied wired to the PCB along with a link to connect the two batteries in...

Page 25: ...of the fire alarm system in accordance with local standards will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Should the control panel become faulty the complete electronic assembly can be replaced To do this any configured options should be noted then both mains and battery power should be removed before the...

Page 26: ...T ACTIVATION Activation of a call point with a 270R resistance fitted is indicated by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 31 ZONE 1 ALARM FROM DETECTOR DELAYED S...

Page 27: ...UND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZONE 4 ANY ALARM DELAYED A5 ZONE 5 ANY ALARM DELAYED A6 ZONE 6 ANY ALARM DELAYED A7 ZONE 7 ANY ALARM DELAYED A8 ZONE 8 ANY ALARM DELAYED C1 ZONE 1 SOUN...

Page 28: ...Man 1078_Sigma_CP_AUS_12 Page 28 of 29 This page intentionally left blank ...

Page 29: ...Man 1078_Sigma_CP_AUS_12 Page 29 of 29 ...

Reviews: