Man-1078_Sigma_CP_AUS_12
Page 18 of 29
Table 8
Configuration Codes
CODE FUNCTION
COMMENTS
00
SOUNDER DELAY TIME = 30 SECONDS
Sets the time delay before sounders operate in combination with
configuration codes 31 to 48 and access level 2 function AD.
01
SOUNDER DELAY TIME = 1 MINUTE
02
SOUNDER DELAY TIME = 2 MINUTES
03
SOUNDER DELAY TIME = 3 MINUTES
04
SOUNDER DELAY TIME = 4 MINUTES
05
SOUNDER DELAY TIME = 5 MINUTES
06
SOUNDER DELAY TIME = 6 MINUTES
07
SOUNDER DELAY TIME = 7 MINUTES
08
SOUNDER DELAY TIME = 8 MINUTES
09
SOUNDER DELAY TIME = 9 MINUTES
10
COMMON ALARM MODE (default)
All sounders operate upon any fire condition
11
TWO-STAGE ALARM MODE
Continuous sounders in activated zone, pulsing elsewhere
12
ZONED ALARM MODE
Only sounders connected to zone in alarm operate
21*
DISABLE FIRE BUZZER
Buzzer will not operate on fire condition
22*
DISABLE FAULT OUTPUT
Fault relay will not operate except upon total power failure
23
DISABLE EARTH FAULT MONITORING
Connection of fire alarm wiring will not announce a fault
24
PULSED REMOTE CONTROL OUTPUT
Aux 24V supply pulses 1 sec on/1 sec off
25
ENABLE SOUNDERS ON DETECTION CIRCUITS
Set as default if panel is two wire “T” series (detectors and call
points on same cables)
26
DISABLE FIRE OUTPUT
Fire relay will not operate upon any alarm
27
REMOVE AUX 24 UPON PANEL RESET
DO NOT SET
24V supply switches off for about 5 seconds when panel is reset
28
INDICATE CALL POINT ACTIVATION
Activation of a call point with a 270R resistance fitted is
indicated by a flashing zone indicator and “
Pu
” on the 7 segment
display. Activation of a detector will be indicated by a steady
zone indicator and nothing on the 7 segment display.
29
DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE
Silenced sounders will not re-sound upon further zone
activations
31
ZONE 1 ALARM FROM DETECTOR DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only.
Note: Access level 2 function Ad must be set for this to take
effect.
32
ZONE 2 ALARM FROM DETECTOR DELAYED
33
ZONE 3 ALARM FROM DETECTOR DELAYED
34
ZONE 4 ALARM FROM DETECTOR DELAYED
35
ZONE 5 ALARM FROM DETECTOR DELAYED
36
ZONE 6 ALARM FROM DETECTOR DELAYED
37
ZONE 7 ALARM FROM DETECTOR DELAYED
38
ZONE 8 ALARM FROM DETECTOR DELAYED
41
ZONE 1 ALARM FROM CALL POINT DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only.
Note access level 2 function Ad must be set for this to take
effect.
42
ZONE 2 ALARM FROM CALL POINT DELAYED
43
ZONE 3 ALARM FROM CALL POINT DELAYED
44
ZONE 4 ALARM FROM CALL POINT DELAYED
45
ZONE 5 ALARM FROM CALL POINT DELAYED
46
ZONE 6 ALARM FROM CALL POINT DELAYED
47
ZONE 7 ALARM FROM CALL POINT DELAYED
48
ZONE 8 ALARM FROM CALL POINT DELAYED
51
COINCIDENCE ZONE 1
Zone contributes to ancillary board coincidence O/P. Any
number of zones can be selected to contribute.
52
COINCIDENCE ZONE 2
53
COINCIDENCE ZONE 3
54
COINCIDENCE ZONE 4
55
COINCIDENCE ZONE 5
56
COINCIDENCE ZONE 6
57
COINCIDENCE ZONE 7
58
COINCIDENCE ZONE 8
61
CONFIGURE Z1 FOR I.S BARRIER
Detection threshold changed for use with IS barrier
62
CONFIGURE Z2 FOR I.S BARRIER
63
CONFIGURE Z3 FOR I.S BARRIER
64
CONFIGURE Z4 FOR I.S BARRIER
65
CONFIGURE Z5 FOR I.S BARRIER
66
CONFIGURE Z6 FOR I.S BARRIER
67
CONFIGURE Z7 FOR I.S BARRIER
68
CONFIGURE Z8 FOR I.S BARRIER