Man-1078_Sigma_CP_AUS_12
Page 8 of 29
Table 4
Compatible Detectors
Model
Type
Manufacturer
Maximum Number per zone
SLV-AS
OPTICAL
HOCHIKI
40
DCD-A
HEAT
HOCHIKI
40
DCD-C
HEAT
HOCHIKI
35
DFJ-60B
HEAT
HOCHIKI
40
DFJ-90D
HEAT
HOCHIKI
35
DFG-60BLKJ
HEAT
HOCHIKI
40
DRD-AS
FLAME
HOCHIKI
25
SPC-AS
BEAM
HOCHIKI
6
Table 5
Compatible detector bases and call points
Model
Type
Manufacturer
Comments
YBN-R/4C
PLAIN BASE
HOCHIKI
YBO-R/4A
LED BASE
HOCHIKI
YBO-R/6PA
LED BASE
HOCHIKI
MUS1A-R470SG-01
CALL POINT
KAC
MUS1A-R470SF-01
CALL POINT
KAC
Table 6
Compatible sounders
Model
Type
Manufacturer
Comments
ROSHNI
FULLEON
SQUASHNI
FULLEON
SQUASHNI MICRO
FULLEON
Table 7
Compatible I.S. barriers
Note: To use detectors and sounders within an intrinsically safe area, the detectors and sounders must be of
an intrinsically safe type and approved for use within the risk category.
Model
Type
Manufac
turer
MTL5061
DETECTION ZONE GALVANIC ISOLATOR
MTL
MTL778ac
SOUNDER CIRCUITS SI AND S2 ONLY
MTL