43
8.
Configure the
Digital Outputs
to be in the desired state when the I3N is put into STOP mode, such
as when a program is being loaded.
a.
By default, outputs will turn ‘OFF’.
b.
Outputs may be set to turn ‘ON’.
c.
Outputs may be set to ‘Hold Last State’.
9.
Configure the
Analog Inputs.
a.
The
Filter Constant
may be set from 0 to 7 to digitally filter the signal as shown in the
following chart.
b.
On some models, the input type may be specified as 4-20mA, 0-20mA, or
0-10V.
10.
Configure the
Analog Outputs.
a.
The
Output Value on STOP
may be set to either ‘Hold Last Value’ or to a specific raw value
from 0-32000 when the I3N is put into STOP mode, such as when a program is being
loaded.
b.
On some models, the Output Mode may be specified as 4-20mA, 0-20mA, or 0-10V.
For Analog Inputs, the
Filter Constant
sets the level of digital filtering according to the following chart.
Digital filtering minimizes noise and jitter, improves effective resolution, and provides adequate speed for
most temperature monitor control applications.