HD1-E CANopen instruction manual
- 20 -
⚫
Example
Example 1: When the inverter at address 3 runs forward, the master station will send following SDO command.
COB-ID
Request code
Object index
Sub-
index
Request data
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
0x603
0x2B
0x01
0x21
0x00
0x01
0x00
0x00
0x00
Example 2: If the slave address=3 and the set value1 is defined to be set frequency, set the frequency to 50.00Hz (set value1=0x1388).
The master station will send following SDO command.
COB-ID
Request code
Object index
Sub-
index
Request data
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
0x603
0x2B
0x00
0x21
0x03
0x88
0x13
0x00
0x00
Example 3: To read the running state of the inverter at address 3, the master station will send following SDO command.
COB-ID
Request code
Object index
Sub-
index
Request data
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
0x603
0x40
0x01
0x20
0x00
0x00
0x00
0x00
0x00
If the inverter is running forward, the master station will return following SDO command.
COB-ID
Request code
Object index
Sub-
index
Request data
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
0x583
0x4B
0x01
0x20
0x00
0x01
0x01
0x00
0x00
Example 4: The slave address is 3 and the set value1 is defined to be running frequency. To read the running frequency of the inverter,
the master station will send following SDO command.
COB-ID
Request code
Object index
Sub-
index
Request data
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
0x603
0x40
0x00
0x20
0x03
0x00
0x00
0x00
0x00
If the running frequency is 50.00Hz, SDO command returned to the master station is as follows.
COB-ID
Request code
Object index
Sub-
index
Request data
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
0x583
0x4B
0x00
0x20
0x03
0x88
0x13
0x00
0x00