MENU/Service/Boiler/Combustion
Menu item
Description
Range
Default
Customised
value
Model
Set the heat generator type
1 ÷ 30
Victrix Zeus Superior 25 = 5
Victrix Zeus Superior 30 = 4
Victrix Zeus Superior 35 = 3
Gas type
Defines the type of gas:
NG = operation with Meth-
ane gas
NG = Methane
LG = operation with LPG
gas
AP = operation with Pro-
pane Air gas
Fan rpm min
Setting of minimum fan
speed (absolute)
450 - 3500 (rpm)
Victrix Zeus Superior 25 = 2150 rpm
Victrix Zeus Superior 30 = 2350 rpm
Victrix Zeus Superior 35 = 2350 rpm
Fan rpm max
Setting of maximum fan
speed (absolute)
3500 ÷ 8300 (rpm)
Victrix Zeus Superior 25 = 6400 rpm
Victrix Zeus Superior 30 = 6950 rpm
Victrix Zeus Superior 35 = 6950 rpm
Fan rpm ign.
Sets burner ignition fan
speed
2000 ÷ 4500 (rpm)
Victrix Zeus Superior 25 = 3800 rpm
Victrix Zeus Superior 30 = 3500 rpm
Victrix Zeus Superior 35 = 3500 rpm
Maximum calibr. range
Activates a greater combus-
tion set adjustment range
during complete calibra-
tion
No = normal combustion
set adjustment range
No
Yes = extended combustion
set adjustment range
A change in values of this table will cause a boiler block with E62 appearing and consequent request for complete calibration.
The P.C.B. defines the operating mode and the boiler output according to the combination of several parameters.
The correct fan revolutions to obtain the correct operating power of the appliance are defined from the combination of param-
eters "Model", "Gas type", "Flue Lenght"; this is why it is suggested not to modify the “Fan rpm” parameters.
MENU/Service/Boiler/Powers
Menu item
Description
Range
Default
Customised
value
Power max DHW
Defines the maximum heat output percentage of
the boiler during the D.H.W. phase compared to
the maximum heat output available
0 ÷ 100 (%)
Victrix Zeus Superior 25 = 100
Victrix Zeus Superior 30 = 83
Victrix Zeus Superior 35 = 100
Power min DHW
Defines the minimum heat output percentage of
the boiler during the D.H.W. phase compared to
the minimum heat output available
0 ÷ 100 (%)
Victrix Zeus Superior 25 = 22
Victrix Zeus Superior 30 = 17
Victrix Zeus Superior 35 = 17
Power max CH
Defines the maximum heat output percentage of
the boiler during the central heating mode com-
pared to the maximum heat output available
0 ÷ 100 (%)
Victrix Zeus Superior 25 = 73
Victrix Zeus Superior 30 = 75
Victrix Zeus Superior 35 = 75
Power min CH
Defines the minimum heat output percentage of
the boiler during the central heating mode com-
pared to the minimum heat output available
0 ÷ 100 (%)
Victrix Zeus Superior 25 = 0
Victrix Zeus Superior 30 = 0
Victrix Zeus Superior 35 = 0
Correction flow DHW
Not used on this model
- 9 ÷ 9 (kw)
0