Page 34
Cascade configuration level.
The parameters included in this section refer to the connection of boilers in cascade. The visualization is possible only when more boilers are controlled
by the regulator.
PARAmETER
Description
Regulation
Setting range / Parameters
01
Common delivery temperature differential
10
0,5 ... 30 K
02
Start delay
0
0 ... 200 Min
03
Stop delay
0
0 ... 60 Min
04
Boilers switching-on heat output
65
10 ... 100 % Nominal heat output
05
Boiler sequence inversal
OFF
OFF, 1 ... 240 h
06
Primary stage
1
1 ... n (stages number)
07
Peak boiler from address
OFF
3 ... n (stages number)
08
Peak boilers change with standard
OFF
OFF, ON
BUS data configuration level.
PARAmETER
Description
Regulation
Setting range / Parameters
01
Regulator BUS address
10
10, 20, 30, 40, 50
02
Configuration of direct circuit remote control
2
1
Parameters modification of all circuits
2
Parameters modification of Direct Circuit only
03
Configuration of mixed circuit 1 remote control
2
1
Parameters modification of all circuits
2
Parameters modification of Mixed Circuit 1 only
04
Configuration of mixed circuit 2 remote control
2
1
Parameters modification of all circuits
2
Parameters modification of Mixed Circuit 2 only