Configuration level for direct / mixed 1 / mixed 2 heating circuits.
These sections include all the necessary parameters to program the direct / mixed heating circuits.
PARAmETER
Description
Regulation DC
Regulation mC 1
Regulation mC 2
Setting range / Parameters
REDUCED HEA-
TING
Reduced/eco functioning mode
ECO
ECO
ECO
ECO
- functioning with stop
RID
- functioning with reduced temp.
HEATING
SYSTEM
Type of heating system
1.3
1.1
1.1
1,00 ... 10,00 (Radiators, Underfloor, etc ...)
03
Room temperature sensor activation
OFF
OFF
OFF
OFF
1
Room sensor activated
2
Room sensor activated, control locked
3
Only for visualization
04
Influence of room sensor over delivery temperature
OFF
OFF
OFF
OFF
10 ... 500 % influence
RC remote control active
05
Automatic heating curve adjustment
OFF
OFF
OFF
OFF, ON
06
Central heating pre-ignition
OFF
OFF
OFF
OFF, 1 ... 16 h
07
Heating circuit restriction
OFF
OFF
OFF
OFF, 0,5 ... 40 K
08
Room anti-freeze temperature
5 °C
5 °C
5 °C
5 ... 30 °C
09
Room thermostat function activation
OFF
OFF
OFF
OFF, 0,5 ... 5 K (differential)
11
Constant temperature nominal value
20°C
20°C
20°C
10 .. 95°C only for fixed regulation (KR)
12
Min. delivery temperature
20 °C
20 °C
20 °C
10 °C ... max. temperature (parameter 13)