IMEON INVERTER
IMEON_installation_guide_rev D.6
83
FR
FR
EN
ES
IT
Code
Type
Description
63
error_ond
AC BACKUP short-circuits. Shutdown the inverter, then unplug the AC BACKUP connector,
then restart the inverter and activate the AC BACKUP by pushing the OK button during 3sec.
If this error is resolved, the issue comes from a connected device on the AC BACKUP
connector. If the problem remains, please contact your distributor.
64
error_ond
Fan failure. Please restart the inverter. If the problem remains, please contact your
distributor.
65
error_ond
AC BACKUP sensor failure. Please restart the inverter. If the problem remains, please
contact your distributor.
66
error_ond
Hardware version detection error. Please restart the inverter. If the problem remains, please
contact your distributor.
67
error_ond
AC Input/Output reversal. This problem may cause a critical electronic damage. Stop the
inverter and check the AC Grid and AC BACKUP connections are not reversed. If the
problem remains, please contact your distributor.
68
error_ond
AC BACKUP undervoltage. Please reboot the inverter and activate the AC BACKUP. If the
problem remains, please contact your distributor.
69
error_ond
AC BACKUP overvoltage. Please reboot the inverter and activate the AC BACKUP. If the
problem remains, please contact your distributor.
70
error_bat
Battery voltage too high. This problem may cause a critical electronic damage. Disconnect
your battery and check if its specifications comply with inverter. If the problem remains,
please contact your battery distributor.
71
error_bat
Battery not connected. Please connect the batteries and check if a breaker/fuse is not open
between inverter and batteries. If the problem remains contact your battery distributor.
72
error_bat
Charging current error. Check battery settings and check the battery connection & voltage. If
the problem remains, please contact your distributor.
73
error_bat
Battery voltage differs from communicated value. There is a communication problem
between inverter and battery BMS. Please reboot the battery and inverter and check the
good connection of battery communication cable. If the problem remains, please contact
your distributor.
74
error_ond
Internal supply failure. Please restart the inverter. If the problem remains, please contact
your distributor.
75
com_lost
CAN communication lost. There is a communication problem between inverter and battery
BMS. Please reboot the battery and inverter and check the good connection of battery
communication cable. If the problem remains, please contact your distributor.
76
error_bat
Battery error reported. Check the battery ID error in OS. ONE, then restart the battery and
the inverter. If the problem remains contact your battery distributor.
77
com_lost
Communication lost between processors. Please reboot the inverter. If the problem remains,
please contact your distributor.
78
com_lost
Internet connection lost. Check your internet connection.
87
error_bat
Battery current exceeds max battery current limit. Please check the good setting of battery
parameter in OS. ONE. If the problem remains contact your battery distributor.
88
error_ond
Power on grid connection overpasses maximum power specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
89
error_ond
Current on grid connection overpasses maximum power specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
90
error_ond
Frequency on AC BACKUP exceeds minimum frequency specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
91
error_ond
Frequency on AC BACKUP exceeds maximum frequency specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
92
error_ond
Current on AC BACKUP overpasses maximum current specification. Remove the high
power devices with inrush power (air conditioner, pumps,...). This problem can cause a
critical electronic damage. If the problem remains contact your distributor.
93
error_ond
PV input power overpasses specification. This problem can cause a critical electronic
damage. Please check the PV sizing, connection and installation. If the problem remains
contact your distributor.
Summary of Contents for 3.6
Page 1: ...GUIDE DE MONTAGE INSTALLATION GUIDE GU A DE MONTAJE GUIDA DI INSTALLAZIONE IMEON...
Page 6: ...ONDULEUR IMEON 6 IMEON_installation_guide_rev D 6 FR FR EN ES ES IT 1 Sch ma de montage...
Page 53: ...IMEON INVERTER IMEON_installation_guide_rev D 6 53 FR FR EN ES IT 1 Wiring diagram...
Page 99: ...INVERSOR IMEON 99 IMEON_installation_guide_rev D 6 FR ES EN IT 1 Diagrama de cableado...
Page 140: ...INVERSOR IMEON 140 IMEON_installation_guide_rev D 6 FR FR ES EN IT Anexo4 Modos de trabajo...
Page 146: ...INVERTER IMEON 146 IMEON_installation_guide_rev D 6 FR FR IT EN ES 1 Schema di montaggio...
Page 188: ......