3.9.2 AC BACKUPConnection for IMEON 9.12
Step 1 :
Wire the connector as defined in paragraph 3.3.
Step2:
Make sure the wires are securely connected.
Step3:
Plug the RST Connector in the AC BACKUP socket.
WARNING:
Before plug-in in the cable, make sure there is no load on the circuit connected to
the AC BACKUP.
WARNING:
AC BACKUP cannot be connected in parrallel to another IMEON and should not be
connected to the grid.
3.10 Temperature sensor
In case the temperature sensor is used, it must be connected to the T.CAP terminal. The temperature
sensor must be placed in the center of the battery bank. When the temperature sensor is connected, the
temperature compensation is 5mV/°C.