Ilumen
10
Installation Manual Ilumen PID Box & Ilumen PID Control Box
Attention:
If you work with inverters with multiple MPPT’s, you cannot mix the PV arrays from
multiple MPPT’s. Standard rule throughout the installation is one Ilumen PID Box for each
MPPT.
Attention:
The maximum current that can passthrough the Ilumen PID Box is 34A. Make sure this is
never exceeded.
Attention:
Make sure the PV arrays are connected to the “PV+” and “PV-“ cables of the Ilumen PID
Box, NEVER to the “+” or “-“ cables.
6.5
I
LUMEN
PID
B
OX SERIES CONNECTION
Connect the 4-pole male connector of the first Ilumen PID Box to the 4-pole female connector of
the Ilumen PID Control Box. Following you can connect up to 100 Ilumen PID Boxes in total in a
series chain by mating each 4-pole female connector from the last chained to the 4-pole male
connector of the one your adding. The end of the chain must be sealed by you in a non-
conductive and weather resistant manner (e.g. by a terminator plug). Make sure the connections
are screwed properly and tightly to insure the connection and the weather resistance.
7
C
OMMISSIONING
7.1
C
HECK
Do a final check whether everything is properly mounted and connected (see
details):
The PV frames are all connected to the same earth as the earth connection of the Ilumen
PID Control Box
Ilumen PID Control Box is fixed firmly against the wall
Ilumen PID Control Box GPRS antenna is placed in a good wireless connectable position
AC cable is correctly connected
PV and inverter DC cables are correctly connected