IKA CBC 5 basic Operating Instructions Manual Download Page 14

14

Proportional coefficient of PID (Kp 1):

Integral time of PID (Ti 1):

Differential time of  PID (Td 1):

The proportional coefficient 

Kp

 is the controller amplifi-

cation and determines how strongly the control deviation 
(the difference between the target temperature and ac-
tual temperature) directly affects the control variable (on-
time of the heater)� 

Kp

 values that are too large can lead 

to the controller overshooting�

The integral time 

Ti

 (s) is the correction time and deter-

mines how strongly the duration of the control deviation 
affects the control variable� 

Ti

 compensates an existing 

control deviation� A high 

Ti

 means a smaller and slower 

effect on the control variable� Ti values that are too small 
can lead to instability of the controller�

The differential time 

Td

 (s) is the derivative time and de-

termines how strongly the rate of change of the control 
deviation affects the control variable� 

Td

 compensates for 

rapid control deviations� A high Td means a smaller and 
slower effect on the control variable� 

Td

 values that are 

too small can lead to instability of the controller�

 External and internal temperature control (ET)

(heating):

ET 0:

 internal temperature control

ET 1:

 external temperature control

If the external temperature control (

ET 1

) is selected, the 

following items 

EuT 2

 (sampling time), 

Kp 2

Ti 2

Td 2

Df t

 (maximum temperature difference between internal 

and external temperature) and 

FAST

 could be set� Other-

wise they are not displayed in the menu list�

The sampling time 

EuT 2

 (s) is the interval over which 

the external control deviation and the respective control 
variable (dependent on 

Kp 2

,

 Ti 2

Td 2

Df t

 and 

FAST

is determined�

EuT 2

 must be adjusted to match the response charac-

teristic (total of all time constants) of the external closed 
loop controlled system, so that the control variable can 
deliver a uniform and measurable change in the control 
deviation� 

EuT 2

 values that are too small or too large 

can lead to instability of the controller�

Dynamics of the external PID temperature control (

FAST

):

FAST=0:

 accurate, without overshoot

FAST=1:

 fast, with overshoot

 Alarm and key tone (BEEP):

BEEP 0: 

no alarm and key tone

BEEP 1: 

alarm and key tone is activated

 Calibration and adjustment (CALI):

CALI 0: 

Reset calibration

CALI 2: 

2-point calibration

CALI 3: 

3-point calibration

Example: 2-point calibration:

Dip the temperature sensor of the reference measuring 
device into the bath fluid: 
- If 

ET 0

: into the internal bath (open the lid (2))

- If 

ET 1

: at the same position as the external Pt100 

temperature sensor (13)�

If 

ET 0

: adjustment of the internal temperature measure-

ment�
If 

ET 1

: adjustment of the external temperature measure-

ment�

Set the first point temperature (e�g� 80 °C)� Confirm the 
setting by pressing the right knob (J)� 

Left area of the display appears the set value (80 °C) and 
the right area of the display appears the actual tempera-
ture value measured� The “Set” LED (B) flashes briefly� 

Select 2-point calibration in the menu� Press the right 
knob (J) to start the 2-point calibration�

 Cooling (COOL):

0: 

Cooling function is deactivated�

1: 

Cooling function is activated�

Summary of Contents for CBC 5 basic

Page 1: ...20000013102 IKA CBC 5 basic CBC 5 basic_112016 Operating instructions EN...

Page 2: ...er 4 Handle 5 Venting grid 6 Mains switch 7 Power socket 8 Cable clip 9 Pump connection IN 10 Pump connection OUT 11 RS 232 interface 12 USB interface 13 External temperature sensor socket Device setu...

Page 3: ...panel and display 10 Setting the safety temperature 11 Commissioning 11 Menu settings 12 Menu structure 12 Basic guide to setting the menu options 13 Operating mode MODE 13 Maximum temperature HI T 13...

Page 4: ...10 2 051 EN 61326 1 EN 60529 and DIN 12876 1 Indicates an extremly hazardous situation which if not avoided will result in death serious injury Indicates a hazardous situation which if not avoided can...

Page 5: ...For example users can implement measures that inhibit fire or explo sions or comprehensive monitoring equipment Process pathogenic material only in closed vessels under a suitable fume hood Please co...

Page 6: ...at also supplies residential areas The safety of the user cannot be guaranteed if the device is operated with accessories that are not sup plied or recommended by the manufacturer if the device is ope...

Page 7: ...ources and do not expose to sun light Cooling machine pump motor and electronics produce intrinsic heat that is dissipated via the venting grids 5 Never cover these venting grids Note After setting up...

Page 8: ...valve is closed Ro tate clockwise to the stop position see Fig 7 Note Please note information in chapter Commissioning Connect the mains plug and turn on the device with mains switch 6 The low level...

Page 9: ...distilled or bi distilled water are unsuitable for operation due to corrosive properties of these media High purity water and distillates are suitable as a medium after adding 0 1 g soda Na2 CO3 sodi...

Page 10: ...speed value Start stop the pump function K Rotating pressing knob Set the temperature value Start stop the heating refrigerating function Navigation selecting the settings in the menu Set and confirm...

Page 11: ...and fan starts to run at once After pressing the mains switch 6 the start up of the com pressor is delayed about 3min In working status press the right knob J to stop the pump function The heating ref...

Page 12: ...play will change back and show pump speed When the heating refrigerating function is activated you can enter the menu option by pressing menu key G about 3 seconds Menu settings MODE Maximum temperatu...

Page 13: ...luid fluid type Note The maximum value is limited by the set safety temperature Minimum temperature LO T The minimum adjustable value 25 C Maximum speed HI R The maximum adjustable value 4600 rpm Mini...

Page 14: ...not displayed in the menu list The sampling time EuT 2 s is the interval over which the external control deviation and the respective control variable dependent on Kp 2 Ti 2 Td 2 Df t and FAST is dete...

Page 15: ...cs of the interface and the al location of signal status standard RS 232 applies in accor dance with DIN 66 259 Part 1 Transmission procedure asynchronous character transmis sion in start stop mode Ty...

Page 16: ...ODE_1 Set to External temperature control OUT_WD1 n Start the watchdog mode 1 and set the time for the watchdog to n 20 1500 seconds Echo of the Watchdog time During a WD1 event the heating and pump f...

Page 17: ...erial Water containing tenside isopropyl alcohol Cosmetics Water containing tenside isopropyl alcohol isopropyl alcohol Water containing tenside Foodstuff Water containing tenside Fuel Water containin...

Page 18: ...off Heating refrigerating off Device internal temperature is too high Check the ambient temperature and let the device cool down Err 10 Pump off Heating refrigerating off PC communication failure Chec...

Page 19: ...be nominal width 12 mm H PUR 8 PUR tube nominal width 8 mm H PUR 12 PUR tube nominal width 12 mm H FKM 8 FKM tube nominal width 8 mm H FKM 12 FKM tube nominal width 12 mm Tubing insulations ISO 8 Insu...

Page 20: ...play LED Heating capacity W 2500 230 VAC 1250 115 VAC Cooling capacity according to DIN 12876 at 4600 rpm 20 C 10 C 0 C 10 C 20 C W 350 400 W at 3200 rpm 320 370 W at 3200 rpm 270 320 W at 3200 rpm 19...

Page 21: ...IKA warranty conditions the warranty period is 24 months For claims under the warranty please contact your local dealer You may also send the machine direct to our factory enclosing the delivery invo...

Page 22: ...IKA Werke GmbH Co KG Janke Kunkel Str 10 D 79219 Staufen Tel 49 7633 831 0 Fax 49 7633 831 98 sales ika de www ika com...

Reviews: