4
Functions and features
3
The pressure sensor detects the system pressure of machines and installations�
Applications
3.1
Type of pressure: relative pressure
Order no.
Measuring range
Permissible
overload pressure Bursting pressure
bar
PSI
bar
PSI
bar
PSI
PI1693
-1���25
-14�4���362�7
100
1 450
350
5 070
PI1694
-1���10
-14�5���145
50
725
150
2 175
PI1695
-1���4
-14�5���58
30
435
100
1 450
PI1696
-0�124���2�5
-1�8���36�24
20
290
50
725
mbar
PSI
bar
PSI
bar
PSI
PI1689
5���100
-0�073���1�45
4
58
30
435
PI1697
-50���1 000
-0�73���14�5
10
145
30
435
PI1698
-12�4���250
-0�18���3�62
10
145
30
435
PI1699
-1 000���1 000 -14�5���14�5
10
145
30
435
MPa = bar ÷ 10 / kPa = bar × 100
Static and dynamic overpressures exceeding the indicated overload pres-
sure are to be avoided by taking appropriate measures�
The indicated bursting pressure must not be exceeded� Even if the bur-
sting pressure is exceeded only for a short time, the unit can be destroyed�
NOTE: Risk of injury!
Function
4
Processing of the measured signals
4.1
The unit displays the current system pressure�
•
It generates 1 output signal according to the parameter setting�
•
OUT
analogue signal 4���20 mA (20���4 mA)
Pressure monitoring/ analogue function
4.2
The analogue signal can be set�
[OU2] defines whether the set measuring range is provided as a 4���20 mA
•
signal ([OU2] = [I]) or a 20���4 mA signal ([OU2] = [InEG])�