Applications (type of pressure: relative pressure)
Avoid static and dynamic overpressure exceeding the given over-
load pressure.
Even if the bursting pressure is exceeded only for a short time
the unit can be destroyed (danger of injuries)!
For gaseous media the application is limited to max. 25 bar.
Before mounting and removing the sensor, make sure that no
pressure is applied to the system.
Mount the pressure sensor on a G¼ process connection.
The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Disconnect power before connecting the unit as follows:
27
ENGLISH
Installation / Electrical connection
1
7
4
3
L+
L-
Out1
2
Out2
5
In-
6
Uref
In+
BN
VT
BK
BU
WH
GY
PK
+
-
InP2
10 V
OU1
OU2
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white),
3 = BU (blue), 4 = BK (black)
5 = GY (grey), 6 = PK (pink)
7 = VT (lilac),
n.c. = not connected.
Bursting
pressure
Permissible
overl. pressure
Measuring
range
Order no.
PNI021
0 ... 250 bar
400 bar
850 bar
PNI022
0 ... 100 bar
300 bar
650 bar
PNI023
0 ... 25bar
100bar
350 bar
PNI024
0 ... 10 bar
50 bar
150 bar