6 Electrical connection
The unit must be connected by a qualified electrician.
Observe the national and international regulations for the installation of electrical equipment.
Voltage supply according to SELV, PELV.
By means of basic insulation according to EN61010-1, the circuits are isolated from each other and
from device surfaces that could be touched (secondary circuit with max. 30 V DC, supplied from mains
circuit up to 300 V overvoltage category II).
CAUTION
Input current is not limited.
w
No fire protection.
u
Protect circuits.
u
Protect circuits.
Potential
M12 connector
①
Fuse
L+ / supply voltage
Pin 1
≤ 2 A
Required tripping characteristic of the fuses:
T
fuse
≤ 120 s at max. 6.25 A (fire protection)
u
Alternatively supply the unit via a limited energy circuit according to IEC 61010-1 or class 2
according to UL1310.
Output reaction to overload or short circuit:
For self-protection of the output in case of excessive thermal load (due to short circuit or
overload), the output driver starts clocking. If a short circuit / overload continues for several
hours, the driver may be damaged!
u
Disconnect power.
u
Connect the unit as follows:
2
1
4
3
2
1
3
1
2
4
5
Fig. 7: Electrical connection
1:
4-pole M12 connector
(output side)
• Pin 1: L+ / supply voltage
• Pin 2: OUT2 / digital output 2
• Pin 3: L- / supply voltage
• Pin 4: OUT1 / digital output 1/ IO-Link (C/Q)
2:
5-pole M12 socket
(input side)
• Pin 1: L+
• Pin 2: IN2 / digital input 2
• Pin 3: L-
• Pin 4: IN1 / digital input 1
• Pin 5: not used
The unit must not be externally supplied via the 5-pole M12 input socket
②
.
Always use the provided connection cables to connect other devices.
See also application examples (
Ò
Intended use)